power the heater and the control circuit. This set up allows the heater to energize when the 
main motor circuit breaker is off for service work or extended shutdowns. The oil heater relay 
status can be viewed on the Status02 screen on the LID. Oil sump temperature can be viewed 
on the LID default screen. 
Software Version 
The software version will always be labeled on the PSIO module, and on the back side of the 
LID module. On both the Controller ID and LID ID display screens, the software version number 
will also appear.
Set Up Machine Control Configuration
As configuration of the 17/19EX unit is performed, write down all configuration settings. A 
log, such as the one shown in 
, provides a convenient list for con-
figuration values.
Do not operate the machine before the control configurations have been checked 
and a Control Test has been satisfactorily completed. Protection by safety con-
trols cannot be assumed until all control configurations have been confirmed.
WARNING
!
WARNING