Configuration 0…10V 
To use the analog inputs with voltages of up to 10V DC, it is neccessary to 
change the jumper configuration. Please pay attention that the keys are free and 
may fall out while opening the case. To avoid this, place the device keys down on the 
table and then gently pull the board out of the case. 
 2 
Following the jumper configuration for input voltages of up to 10 V. 
 
 
Analog 0 
Analog 1 
Analog 2 
Analog 3 
 
J11 J12 J13 J15 J14 J17 J16 J18 
0-10V 
1 -3 
1 - 3 
1 –3 
1 -3 
1 -3 
1 -3 
1 –3 
1 -3 
 
Configuration 0...20mA 
The past configurations have been voltage inputs. The following configuration 
makes it possible to realize current inputs. 
 
 
Analog 0 
Analog 1 
Analog 2 
Analog 3 
 
J11 
J12 J13 J15 J14 J17 J16 J18 
0-20mA 
1 -2 
1 - 2 
1 -2 
1 - 2 
1 - 2 
1 - 2 
1 - 2 
1 - 2 
 