Environmental Specifications 
Backboard Mounting Hardware Requirements
This refers to the types of wall construction to which the backboard 
will be attached.
Hardware has a combined pullout force of 650 lb. (294.8 kg). When 
mounting to sheet-metal walls, attach to structural members.
Location
Within 5 feet (1.5 m) of dedicated AC power outlet (1 plug per 
carrier).
Within 1000 cable feet (304.8 m) of telephones.
Heat Dissipation
Fully loaded basic carrier 
500 Btu/hr (35 cal/sec)
Fully loaded 2-carrier system
1000 Btu/hr (70 cal/sec)
(basic carrier with one expansion carrier)
Fully loaded 3-carrier system
1500 Btu/hr (105 cal/sec)
(basic carrier plus two expansion carriers)
Power Requirements
Basic carrier 117 VAC
60 Hz -15% to 10%    5.4A
2-carrier 117 VAC
60 Hz -15% to 10% 10.8A
3-carrier 117 VAC
60 Hz -15% to 10% 16.2A
Temperature/Humidity Range
40°–104°F (4°–40°C)
20%-80% relative humidity
Ventilation Clearances
1 inch (2.5 cm) on right and left sides
Radio Frequency Interference, Tolerance
1.0 V/m
Electromagnetic Interference (EMI)
To reduce electromagnetic interference emissions (possible 
interference problems with handheld telephones), check the date of 
manufacture of the CPU (517A27) units. If they were manufactured 
before April, 1993, replace them with a later version.
 CAUTION:
!
For the control unit, do not use an AC outlet that is controlled 
by a wall switch or some other switch.
Use an approved ground (AC receptacle for 3-prong plug).
Do not install the control unit outdoors.
Do not place the control unit near extreme heat (furnaces, 
heaters, attics, or direct sunlight).
Do not expose the control unit to devices that generate 
electrical interference (such as arc welders or motors).
Type of material 
Mounting Hardware 
Wood surface
Wood screws
Concrete surface, brick, cinder block
Masonry anchors
Plaster, plasterboard
Toggle bolts
Sheet-metal surface
Sheet-metal screws