Generac QT04524KNSX User Manual

Page of 4
QT045
KW RATING 
45
ENGINE SIZE 
2.4 Liter
GENERATOR OUTPUT VOLTAGE/KW - 60Hz 
KW 
AMP 
CB Size
 120/240V, 1-phase, 1.0 pf
45
188
200
 120/208V, 3-phase, 0.8 pf
45
156
175
 120/240V, 3-phase, 0.8 pf
45
135
150
 277/480V, 3-phase, 0.8 pf
45
68
80
GENERATOR LOCKED ROTOR KVA
 AVAILABLE @ VOLTAGE DIP OF 35%
 Single phase or 208/240 3-phase
100
 480V 3-phase
110
ENGINE FUEL CONSUMPTION 
(Natural Gas) (Propane)
  
Natural Gas
Propane
   
 
 (ft
3
/hr.)
(gal/hr.)
cu ft/hr
 Exercise cycle
102
1.11
40.4
 25% of rated load
194
2.12
77.1
 50% of rated load
373
4.07
148
 75% of rated load
520
5.67
206.3
 100% of rated load
720
7.86
286
ENGINE COOLING
  
Air flow
(inlet air including alternator and combustion air)
  ft
3
/min.
2,725
 System coolant capacity
US gal.
3.0
 Heat rejection to coolant
BTU/hr.
173,000
 Max. operating air temp. on radiator
°C (°F)
60 (150)
 Max. ambient temperature
°C (°F)
50 (140)
COMBUSTION AIR REQUIREMENTS
  
Flow at rated power 60 Hz
cfm
144
SOUND EMISSIONS IN DBA
 Exercising at 7 meters
61
 Normal operation at 7 meters
73
EXHAUST
 Exhaust flow at rated output 60 Hz
cfm
429
 Exhaust temp. at muffler outlet
°F
1150
ENGINE PARAMETERS
  
Rated synchronous RPM
60 Hz
3600
 HP at rated KW
60 Hz
71
POWER ADJUSTMENT FOR AMBIENT CONDITIONS
 Temperature Deration
 
3% for every 10 °C above - °C
25
 
1.65% for every 10 °F above - °F
77
 Altitude Deration
 
1% for every 100 m above - m
183
 
3% for every 1000 ft. above - ft.
600
OPERATING DATA
QT045
RATING:   All three phases units are rated at 0.8 power factor. All single phase units are rated at 1.0 power factor. STANDBY RATING: Standby
ratings apply to installations served by a reliable utility source. The standby rating is applicable to varying loads for the duration of a power outage.
There is no overload capability for this rating. Ratings are in accordance with ISO-3046-1. Design and specifications are subject to change without
notice.
KW rating is based on LPG Fuel and may derate with natural gas.