Delta DVP-EH Leaflet

Page of 2
http://www.delta.com.tw/products/plc.asp
                                 
 
                       
 
DVP-EH 
DVP04PT-H 
Platinum Temperature Sensors 
Instruction Sheet 
 
1   
WARNING 
 
Please carefully read this instruction thoroughly prior to use the DVP04PT-H. 
   
In order to prevent electric shock, do not touch the terminals or conduct any maintenance while 
power to the PLC is ON.
 
Do NOT open the PLC. Only qualified personel or Delta staff is allowed 
to conduct any internal electrical work on the PLC.   
 
This is an OPEN-TYPE device, and was certified to meet the IEC 61131-2 (UL 508) safety 
requirements when installed in an enclosure.     
 The DVP04PT-H must be kept under the environment away from high temperatures, high 
humidity, exceessive vibration, corrosive gases, liquids, airborne dust, and metallic particles.   
   
Do not apply AC power to any of the input/output terminals, or it may damage the DVP04PT-H. 
  Make sure that the DVP04PT-H is properly grounded 
, to prevent any electromagnetic noise. 
 
Use wires with resistance when connect the platinum resistance thermister (RTD) to PLC.
 
 
Please keep the wires as short as possible when connecting the RTD to PLC, and keep power 
wires as far away as possible from I/O wires to prevent noise interference.
 
2  
INTRODUCTION 
2.1  Model Explanation and Peripherals 
 
Thank you for choosing DELTA DVP PLC Series. DVP04PT-H allows the connection of four 
platinum temperature sensors (PT100 3-WIRE 100 Ω  3850 PPM/
°C (DIN 43760 JIS 
C1604-1989)). The DVP-PLC EH MPU converts the sensors input into a 14 bit digital signal, and     
then be manipulated by using TO and FROM instructions in the ladder logic program.    There are 
49 Controlled Registers (CR, each register has 16 bits) in each module. 
 
Software version DVP04PT-H platinum temperature sensors can be updated via RS-485 
communication. 
 
DVP04PT-H displays both Centigrade and Fahrenheit. The input resolution for Centigrade is 0.1 
degrees and for Fahrenheit is 0.18 degrees. 
 
Nameplate Explanation 
0.1  C or 0.18  F
20.4VDC ~ 28.8VDC
VX.XX
04PT-H0T4250003
PLC model
Input Power Supply Spec.
Analog Input / Output  Module Spec.
Barcode
 
 
Model Explanation 
Model
Serial Number
Product Series
Input+Output point
Model type
AD: Analog input module
DA: Analog output module
PT: Platinum temperature sensors(PT-100)
TC: Thermocouple sensors(Type J/K)
S: for SS series MPU
P: for EP series MPU
H: for EH series MPU
Production week
Production place (Taoyuan)
Production year (2004)
Production Model
XA: A/D , D/A Functions
RT: Resistor Thermocouple
HC: High speed count input module
PU: single axis positioning unit
 
2.2  Product Profile and Outline 
 
 
1. DIN rail track (35mm) 
6. Terminals 
2. Mounting hole for wire to connect extension 
unit/extension module 
7. Mounting hole 
3. Model name 
8. Terminal layout 
4. Indicator for power, error and run status 
9. Mounting port to connect extension 
unit/extension module 
5. DIN rail clip 
 
 
2.3 External 
wiring 
PT100
PT100
CH1
CH4
1mA
DC/ DC
5V
AG
+15V
-15V
AG
AG
AG
24+
24-
FG
I-
L-
L+
FG
I-
L-
L+
Converter
System
Class 3 Grounding
(100    of less)
terminal of
power module
Shielded*1
*2
*3
1mA
Shielded*1
Grounding
Note 1: Use only the wires that are packed 
with the temperature sensor (PT 100) 
for analog input and separate from 
other power line or any wire that may 
cause noise. Please use 3wire for PT 
100. 
Note 2: Terminal FG is a ground location for 
noise suppression.   
Note 3: Please connect 
 power supply 
module terminal and 
 DVP04PT-H 
platinum temperature sensors module 
terminal to system earth ground or 
connect it to machine cover. 
Warning: DO NOT connect wires to the No 
Connection (●) terminals.
 
 
3  
STANDARD 
SPECIFICATIONS 
3.1 Function 
Specifications 
Platinum Temperature Module 
(04PT) 
Centigrade (°C) 
Fahrenheit (°F) 
Power supply voltage 
24 VDC (20.4VDC~28.8VDC) (–15%~+20%) 
Analog input channel 
4 channels per module 
Sensors type 
3-WIRE PT100Ω 3850 PPM/°C(DIN 43760 JIS C1604-1989) 
Current excitation 
1mA 
Temperature input range 
-200°C~600°C  
-328°F~1112°F 
Digital conversion range 
K-2000~K6000 K-3280~K11120 
Resolution 
14 bits (0.1°C) 
14 bits (0.18°F) 
Overall accuracy 
±0.5% of full scale of 25°C(77°F), ±1% of full scale during 0~55°C 
(32~131
°F) 
Response time 
200 ms  × channels 
Isolation Method 
Isolation between digital and analog circuitry. But no isolation 
between channels. 
Digital data format 
2’s complement of 16-bit, (13 Significant Bits) 
Average function 
Yes (CR#2~CR#5 may be set and the range is K1~K4096) 
Self diagnostic function 
Upper bound and lower bound detection per channel 
Communication mode (RS-485)
Yes, either ASCII or RTU modes, communication rate can be 
4800 /9600 /19200 /38400 /57600 /115200. Communication 
format of ASCII mode is 7Bit, even bit, 1 stop bit (7 E 1). 
Communication format of RTU mode is 8Bit, even bit, 1 stop bit (8 
E 1). When connecting to PLC MPU in series, RS-485 can’t be 
used. The RS-485 is disabled when the DVP04PT-H is connected 
in series to an MPU (use the RS485 on MPU). 
Connection to a DVP-PLC MPU 
in series 
When DVP04PT-H modules are connected to an MPU, the 
modules are numbered from 0 – 7. 0 is the closest and 7 is the 
furthest to the MPU. 8 modules is the max and they do not occupy 
any digital I/O points of the MPU. 
3.2 Other 
Specification 
Power Specification 
Maximum Power Consumption 
2W at 24 VDC (20.4VDC~28.8VDC) (-15 % ~ + 20%) 
 
Environment Condition 
Environment Condition 
Follow the DVP-PLC MPU. 
Static Electricity Prevention 
All places between terminals and ground comply with the spec 
 
4
CR (CONTROLLED REGISTER) 
 
DVP04PT-H platinum temperature sensors 
Explanation 
CR
No.
RS-485 
Parameter 
address 
Latched Register 
name b15 
b14 
b13 b12 b11 b10 b9
b8
b7
b6
b5
b4
b3
b2
b1
b0
#0
H 4064  ○  R 
Model type 
System used, data length is 8bits (b7~b0). DVP04PT-H model code = H 0402 
#1 Reserved 
#2
H 4066  ○  R/W  CH1 average number 
#3
H 4067  ○  R/W  CH2 average number 
#4
H 4068  ○  R/W  CH3 average number 
#5
H 4069  ○  R/W  CH4 average number 
The number piece of readings used for the calculation of “average” temperature 
on channels CH1~CH4.     
Setting range is K1~K4096 and factory setting is K10. 
#6
H 406A  ╳  R 
CH1 average degrees(°C) 
#7
H 406B  ╳  R 
CH2 average degrees(°C) 
#8
H 406C  ╳  R 
CH3 average degrees(°C) 
#9
H 406D  ╳  R 
CH4 average degrees(°C) 
Average degrees for channels CH1~CH4.    (unit: 0.1 degrees C) 
#10~ #11 
Reserved 
#12
H 4070  ╳  R 
CH1 average degrees(°F) 
#13
H 4071  ╳  R 
CH2 average degrees(°F) 
#14
H 4072  ╳  R 
CH3 average degrees(°F) 
#15
H 4073  ╳  R 
CH4 average degrees(°F) 
Average degrees for channels CH1~CH4.    (unit: 0.1 degrees F) 
#16~ #17 
Reserved 
#18
H 4076 
  R 
Present temperature of 
CH1 (°C) 
#19
H 4077 
  R 
Present temperature of 
CH2 (°C) 
#20
H 4078 
  R 
Present temperature of 
CH3 (°C) 
#21
H 4079 
  R 
Present temperature of 
CH4 (°C) 
Present temperature of channels CH1~CH4. (unit: 0.1 degrees C) 
#22~ #23 
Reserved 
#24
H 407C 
  R 
Present temperature of 
CH1 (°F) 
#25
H 407D 
  R 
Present temperature of 
CH2 (°F) 
#26
H 407E 
  R 
Present temperature of 
CH3 (°F) 
#27
H 407F 
  R 
Present temperature of 
CH4 (°F) 
Present temperature of channels CH1~CH4. (unit: 0.1degrees F) 
#28~ #29 
Reserved 
#30
H 4082  ╳  R 
Error status 
Data register stores the error status. Refer to the fault code chart for details. 
#31
H 4083  ○ 
R/W Communication address 
setting 
RS-485 communication address.   
Setting range is 01~255 and factory setting is K1 
#32
H 4084  ○  R/W  Communication baud rate 
setting 
Communication baud rate (4800, 9600, 19200, 38400, 57600 and 115200 bps). 
Communication format: ASCII mode is 7Bit, even bit, 1 stop bit (7 E 1). 
Communication format of RTU mode is 8Bit, even bit, 1 stop bit (8 E 1). 
b0: 4800 bps (bit/sec). 
b1: 9600 bps (bit/sec).    (factory setting) 
b2: 19200 bps (bit/sec). 
b3: 38400 bps (bit/sec). 
b4: 57600 bps (bit/sec). 
b5: 115200 bps (bit/sec). 
b6~b13: Reserved. 
b14: switch between low bit and high bit of CRC code (RTU mode only) 
b15: RTU mode.   
b15 b14  b13 b12 b11 b10 b9
b8
b7
b6
b5
b4
b3
b2
b1
b0
Definition of ERR 
LED 
CH4 CH3  CH2  CH1 
#33
H 4085  ○  R/W  Reset to factory setting 
Example: Setting of CH1 
1. b0 Reserved 
2. b1 Reserved 
3. b2: Set to 1 and PLC will be reset to factory settings. 
Definition of ERR LED: b12~b15=1111(factory settings) 
1.  b12 corresponds to CH1:    when b12=1, scale exceeds the range or external 
contact has no connection, ERR LED flashes. 
2.  b13 corresponds to CH2: when b13=1, scale exceeds the range or external 
contact has no connection, ERR LED flashes. 
3.  b14 corresponds to CH3: when b14=1, scale exceeds the range or external 
contact has no connection, ERR LED flashes. 
4.  b15 corresponds to CH4: when b15=1, scale exceeds the range or external 
contact has no connection, ERR LED flashes. 
#34
H 4086  ○  R 
Software version 
Display software version in hexadecimal.    Example: H 010A = version 1.0A. 
#35~#48 System 
used 
 means latched.  
 means not latched. 
R means read data by using FROM instruction or RS-485.   
W means write data by using TO instruction or RS-485. 
Explanation: 
1. CR#0: The PLC model type.   
2. CR#1, CR#10, CR#11, CR#16, CR#17, CR#22, CR#23, CR#28, CR#29 are reserved. 
3. CR#2 ~ CR#5: Used to set the number piece of input readings used for the average temperature 
calculation. The available range is K1~K4096 and factory setting is K10.   
4. CR#6 to CR#9: The average temperature (
°
C
). Temperature
 
is calculated by averaging multiple 
pieces temperature readings.  Example: If CR#2 is 10, the temperature in CR#6 will be the 
average of the last 10 readings on CH1. 
5. CR#12 to CR#15: The average temperature (
°
C
).  Temperature
 
is calculated by averaging multiple 
pieces temperature readings.  Example: If CR#2 is 10, the temperature in CR#12 will be the 
average of the last 10 readings on CH1. 
6. CR#18 ~ CR#21: display the present temperature (
°
C
) of CH1~CH4 input signal. 