DEFINITY Enterprise Communications Server Release 6
Installation and Test for Compact Modular Cabinets  
555-230-128  
Issue 3
May 1998
Install and Cable the Cabinets 
Page 1-14
AC Power and Ground 
1
AC Power and Ground
!
CAUTION:
The AC power circuit must be dedicated to the system. The circuit must not be shared 
with other equipment and must not be controlled by a wall switch. The AC receptacle 
must not be located under the Main Distribution Frame and must be easily accessible.
!
CAUTION:
Removing the 650A Power Unit does not remove AC power from the cabinet. To 
remove AC power, pull the AC power cord from the AC appliance inlet.
!
CAUTION:
System grounding must comply with the general rules for grounding provided in Article 
250 of the National Electrical Code (NEC), National Fire Protection Agency (NFPA) 70, 
or the applicable electric code in the country of installation. 
!
CAUTION:
AC mains wiring and testing must be performed by a qualified electrician and must 
conform to Article 250 of the National Electrical Code (NEC), National Fire Protection 
Agency (NFPA) 70, or the applicable electric code in the country of installation. 
Check AC Power
Each CMC uses an auto-ranging 85 to 264 VAC power supply, 47 to 63 Hz, 330 
Watts, 4.5 Amps (100-120 VAC) or 2.3 Amps (200 to 240 VAC), at 500 VoltAmps 
(VA). The AC power source can be 1 phase of 120 VAC with neutral (100 VAC for 
Japan) with 15 Amp circuit breaker, or 1 phase of 220 or 240 VAC (200 VAC for 
Japan) with 10 Amp circuit breaker. The AC cord uses a NEMA 5-15P plug or an 
IEC 320 plug.
Before powering up the system, check the AC power in the equipment room 
using a KS-20599 digital voltmeter (DVM) (or equivalent).
1. Measure the AC voltage between the hot and neutral side of the 
receptacle.
2. Depending on the AC power source, verify that the meter reads 90 to 132 
VAC or 180 to 264 VAC. If not, have a qualified electrician correct the 
problem.
3. Measure the voltage between the neutral and ground side of the 
receptacle.
4. Verify that the meter reads 0 VAC. If not, have a qualified electrician 
correct the problem.
5. When finished, set the AC mains circuit breakers to 
OFF