Install and Cable the Cabinets 
Page 1-67
Connect External Alarms and Auxiliary Connections 
1
Connect External Alarms and 
Auxiliary Connections
NOTE:
The AUX connector is part of the Processor Interface cable assembly (J1).
Alarm Input
Alarms can be generated on adjunct equipment, sent to the DEFINITY System, 
and recorded and reported as “external alarms.” A typical major alarm 
input
 is 
from a UPS.
1. Connect 1 major and 1 minor alarm 
input
 pair to the trunk/auxiliary field 
from the AUX connector (J1 on Processor Interface Cable). See 
Table 
1-10
.
Alarm Output
The system provides a relay contact that can operate a customer-provided 
alarm, such as a light or bell. The circuitry and power source are customer- 
provided. The alarm device must not exceed a rating of more than 30 VAC RMS 
or 60 VDC at 0.75 Amps. 
1. Connect the external alarm 
output
. See 
Table 1-11
.
2. Give this information to your Lucent Technologies representative for 
troubleshooting purposes.
Table 1-10.
Alarm Inputs at AUX Connector
Color
AUX Connector
White-Blue
AP1 (Pin 26) Major Alarm Input 
Blue-White
Ground (Pin 1)
White-Orange
AP2 (Pin 27) Minor Alarm Input 
Orange-White
Ground (Pin 2)
Table 1-11.
Alarm Output at AUX Connector
Color
AUX Connector
Violet-Green
EXTALMA (Pin 48) Alarm Output
Green-Violet
EXTALMB (Pin 23) (Ground) Alarm Output