Micrologic™ 2.0A, 3.0A, 5.0A, and 6.0A Electronic Trip Units
 48049-136-05
Section 4—Trip Unit Replacement
Rev. 01, 07/2012
© 1999–2012 Schneider Electric All Rights Reserved
30-EN
ENGLISH
Trip Unit Installation
1. Inspect trip unit connector pins and surfaces. 
If there is any damage, misaligned pins, or 
contamination, stop installation and contact 
the local sales office for factory authorized 
service.
2. Inspect trip unit mounting base on the circuit 
breaker. Clear any debris from area and 
check that all accessory wiring is properly 
routed for the trip unit being installed. If there 
is any damage or contamination, stop 
installation and contact the local sales office 
for factory authorized service.
3. For Masterpact NW circuit breaker only: 
Manually depress trip unit interlock (A) and 
hold it in place during steps 4–6 below.
4. Align guide rail (B) on bottom of trip unit with 
guide rail slot (C) on trip unit mounting base 
in circuit breaker and gently slide the trip unit 
in until it stops.
NOTE: The Masterpact NT and NW trip unit 
mounting bases are shock mounted and 
therefore can flex slightly.
Figure 45:
Install Trip Unit
06135453
06135451
Masterpact NW Circuit Breaker 
A
C
B
NOTICE
HAZARD OF EQUIPMENT DAMAGE
Check installation of trip unit to assure proper 
connections and seating.
Failure to follow this instruction can result 
in equipment damage or improper circuit 
breaker tripping.