Micrologic™ 2.0A, 3.0A, 5.0A, and 6.0A Electronic Trip Units
Rev. 01, 07/2012
Section 1—General Information
© 1999–2012 Schneider Electric All Rights Reserved
5-EN
EN
G
L
ISH
Section 1—General Information
Communications
Micrologic trip units can communicate with other devices if the optional 
Circuit Breaker Communication Module (BCM) is installed. For information 
on the communication module, see the product catalog and Modbus™ 
Communications System, Data Bulletin 0613IB1201.
Trip Unit Settings
On the face of the trip unit are adjustable switches to allow changing of trip 
characteristics. Trip units are shipped with the long-time pickup switch set at 
1.0 and all other trip unit adjustments set at their lowest settings.
Introduction
Micrologic™ trip units (A) provide adjustable 
tripping functions on electronic trip circuit 
breakers. The product name (B) specifies the 
level of protection provided by the trip unit.
Micrologic trip units are field replaceable to allow 
for upgrading of the trip unit in the field. For 
complete information on available circuit breaker 
models, frame sizes, interrupting ratings, sensor 
plugs, rating plugs and trip units, see the product 
catalog.
Figure 1:
Micrologic Trip Unit
Micrologic 3.0A
Type of protection
2—Basic IEC protection (LS0)
5—Selective protection (LSI)
6—Selective protection plus ground fault 
Trip unit series
0—Indicates the first version
Type of measurement
None—Provides protection only
A—Provides protection plus ammeter measurements
protection for equipment (LSIG)
3—Basic UL protection (LI)
.4
.5
.6
.7
.8 .9
.95
.98
1
.5
1
2
4
8 12
16
20
24
long
 time
alarm
Ir
tr
(s)
x In
@
 
6 Ir
Micro
logic
 7.0 A
40
100 %
%
men
u
06133249
   
  
06134858
A
B
D
E
C
A—Micrologic Trip Unit
B—Product Name
C—Switch Cover
D—Switch Cover Opening Slot
E—Adjustable Rating Plug