Trane CNT-SVX07C-EN User Manual

Page of 84
Additional components
CNT-SVX07C-EN
5
returns the valve to normally open or closed (dependent on the desired 
default position). For modulating valve control, use tri-state modulating 
actuators with or without a spring return, as required by the application.
Damper actuators
Damper actuators cannot exceed 12 VA draw at 24 Vac. For control of out-
door/return air dampers, use tri-state modulating actuators that incorpo-
rate a spring return.
Zone humidity sensor
For measurement of relative humidity (RH), the Tracer ZN521 requires a 
zone humidity sensor with a 4–20 mA output, where 4 mA is 0% RH and 
20 mA is 100% RH. The controller provides 20 Vdc to power the zone 
humidity sensor. 
CO
2
 sensor
For CO
2
 measurement, the Tracer ZN521 requires a CO
2
 sensor with a 4–
20 mA output, where 4 mA = 0 ppm and 20 mA = 2000 ppm. 
Table 1. Tracer zone temperature sensor options
BAS 
order 
number
Use
Fan
Zone
Timed 
override 
buttons
Comm 
jack
High
Med
Low
Auto
Off
Setpoint 
thumb-
wheel
Temperature 
sensor
On
Cancel
4190 1087
Any
x
4190 1088
Any
x
x
x
x
4190 1090
Any
x
x
x
x
x
4190 1094
Any
x
x
x
4190 1095
Unit 
ventilator
x
x
x
x
x
x
x
x
4190 1115
Fan coil
x
x
x
x
x
x
x
x
x
x
4190 1116
Unit 
ventilator
x
x
x
x
x
x
x
x
x
4190 1117
Any
x
x
x
x
x
x
x