Trane CNT-SVX07C-EN User Manual
CNT-SVX07C-EN
35
Chapter 5
Sequence of operations
The Tracer ZN521 zone controller will operate to maintain the zone tem-
perature setpoint. This chapter discusses many of the operational
sequences used by the controller to accomplish this goal.
perature setpoint. This chapter discusses many of the operational
sequences used by the controller to accomplish this goal.
Power-up sequence
When 24 Vac power is initially applied to the Tracer ZN521 zone control-
ler, the following sequence occurs:
ler, the following sequence occurs:
1.
The green status indicator LED turns on (see “Interpreting LEDs” on
page 56).
page 56).
2.
All outputs are controlled off. All modulating valves and dampers
close, and the face-and-bypass damper calibrates to bypass (when
present).
close, and the face-and-bypass damper calibrates to bypass (when
present).
3.
The controller reads all input local values to determine initial values.
4.
The random-start timer begins (see “Random start” on page 35).
5.
If a hard-wired zone-temperature value is not detected, the controller
begins to wait for a communicated value. (This can take several min-
utes [15-minute default] and occurs concurrently with the remainder
of the power-up sequence.)
begins to wait for a communicated value. (This can take several min-
utes [15-minute default] and occurs concurrently with the remainder
of the power-up sequence.)
6.
The random-start timer expires.
7.
The power-up control wait function begins automatically if the config-
ured power-up control wait time is greater than 0 seconds. When this
function is enabled, the controller waits for the configured amount of
time (from 0 to 120 seconds) to allow a communicated occupancy
request to arrive. If a communicated occupancy request arrives, nor-
mal operation can begin. If a communicated occupancy request does
not arrive, the controller assumes stand-alone operation.
ured power-up control wait time is greater than 0 seconds. When this
function is enabled, the controller waits for the configured amount of
time (from 0 to 120 seconds) to allow a communicated occupancy
request to arrive. If a communicated occupancy request arrives, nor-
mal operation can begin. If a communicated occupancy request does
not arrive, the controller assumes stand-alone operation.
8.
Normal operation begins assuming no diagnostics have been
generated.
generated.
Random start
Random start is intended to prevent all units in a building from energiz-
ing at the same time. The random-start timer delays the fan and any
heating or cooling start-up from 5 to 30 seconds. If neither heating nor
cooling is initiated, or if fan operation is not required during the delay, the
random-start timer will time-out.
ing at the same time. The random-start timer delays the fan and any
heating or cooling start-up from 5 to 30 seconds. If neither heating nor
cooling is initiated, or if fan operation is not required during the delay, the
random-start timer will time-out.