Filter-maintenance timer
The filter-maintenance timer tracks the amount of time (in hours) that 
the fan is enabled. The Maintenance Required Timer Setpoint (config-
urable using the Rover service tool) is used to set the amount of time until 
maintenance (typically, a filter change) is needed. If the setpoint is config-
ured to zero, the filter-maintenance timer is disabled.
The controller compares the fan-run time to Maintenance Required Timer 
Setpoint. Once the setpoint is reached, the controller generates a Mainte-
nance Required diagnostic. When the diagnostic is cleared, the controller 
resets the filter-maintenance timer to zero, and the timer begins accumu-
lating fan-run time again.
Freeze avoidance
Freeze avoidance is used for low ambient temperature protection. It is ini-
tiated only when the fan is off. The controller enters the freeze-avoidance 
mode when the outdoor air temperature is below the Freeze Avoidance 
Setpoint (configurable using the Rover service tool). The controller dis-
ables freeze avoidance when the outdoor air temperature rises 3°F (1.7°C) 
above the Freeze Avoidance Setpoint.
When the controller is in freeze-avoidance mode:
Valves are driven open to allow water to flow through the coil
Fan is off
Face-and-bypass damper (when present) is at full bypass
Economizing is disabled
The outdoor/return air damper is closed
DX cooling is off
Electric heat stages are off
Freeze protection (discharge air temperature low limit) 
The controller monitors the discharge air temperature with a 10 k
Ω ther-
mistor wired to analog input AI2. The freeze-protection operation is initi-
ated whenever the discharge air temperature falls below the Discharge 
Air Temperature Low Limit. The Discharge Air Temperature Low Limit 
is configurable using the Rover service tool. During freeze protection, the 
controller increases the heating capacity or decreases the cooling capacity 
in order to raise the discharge air temperature above the low limit. If the 
discharge air temperature remains below the low limit for 3 minutes, the 
controller generates a Discharge Air Temp Limit diagnostic. See Table 16 
on page 59 f
or the effects of this diagnostic on outputs.