Trane Tracer User Manual

Page of 32
5
Power Up
Sequence
Power Up Sequence
When 24 
VAC
 power initially is 
applied to the ZN510 controller, the 
following sequence occurs:
1.
All outputs are controlled off.
2.
The controller reads all inputs 
to determine their initial values.
Note: Because the space tempera-
ture can be hardwired to the con-
troller or communicated, the 
controller waits for several minutes 
to check for the presence of a com-
municated value.
3.
A random start time is hard 
coded on every board and 
cannot be disabled. The board 
generates a random time delay 
between 0 and 25 seconds. 
Once this time expires, the 
power up control wait time (if 
configured) will wait for 120 
seconds. The power up control 
wait allows ample time for a 
communicated request to 
arrive. If the power up control 
wait time expires, and the 
controller does not receive a 
communicated occupancy 
command, the unit assumes 
stand alone operation.
4.
Normal operation begins.