Honeywell W7750A User Manual

Page of 116
EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER
17
74-2958—1
Fig. 8. DIN rail adapters.
The FTT supports polarity insensitive free topology wiring. 
This frees the system installer from wiring using a specific bus 
topology. T-tap, star, loop, and mixed wiring topologies are all 
supported by this architecture. The maximum L
ON
W
ORKS
 Bus 
length when using a combination of T-tap, star, loop, and bus 
wiring (singly terminated) is 1640 ft. (500m) with the maximum 
node-to-node length of 1312 ft. (400m). In the event that the 
total wire length is exceeded, then a Q7740A 2-Way Repeater 
or a Q7740B 4-Way Repeater can be used to allow the 
number of devices to be spread out as well as increasing the 
length of wire over which they communicate. The maximum 
number of repeaters per segment is one (on either side of the 
router). A Q7751A,B L
ON
W
ORKS
 Bus Router can also be used 
to effectively double the maximum L
ON
W
ORKS
 Bus length. 
The advantage of using the router is that it segregates traffic 
to a segment while when using the repeater, all traffic is 
repeated on each segment. When utilizing a doubly 
terminated L
ON
W
ORKS
 Bus structure, use a continuous daisy-
chain with no stubs or taps from the main backbone, The 
maximum L
ON
W
ORKS
 Bus length is 4593 ft. (1400m) with the 
maximum node-to-node length of 3773 ft. (1150m).
FTT networks are very flexible and convenient to install and 
maintain, but it is imperative to carefully plan the network 
layout and create and maintain accurate documentation. This 
aids in compliance verification and future expansion of the 
FTT network. This also keeps unknown or inaccurate wire run 
lengths, node-to-node (device-to-device) distances, node 
counts, total wire length, inaccurate repeater/router locations, 
and misplaced or missing terminations minimized. Refer to 
L
ON
W
ORKS
 Bus Wiring Guidelines form, 74-2865 for complete 
description of network topology rules.
L
ON
M
ARK
® FUNCTIONAL PROFILE
W7750 Controllers support the L
ON
M
ARK
 Functional Profile 
number 8030 Roof Top Unit Controller, version 1.0 
(see Fig. 9).
M6857
1
2
3