Honeywell W7750A User Manual

Page of 116
EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER
49
74-2958—1
1.
Check the version numbers of the controller firmware, 
E-Vision and the E-Vision script.
2.
Check the wiring to the power supply and make sure 
there is a good earth ground to the controller.
3.
Check the occupancy and HVAC modes.
4.
Compare the current actual setpoint with the actual 
space temperature.
5.
Check the desired configuration settings.
6.
Check the network wiring and type of wire used.
7.
Check the Zone Manager mapping and referred points.
NOTE:
If the fan shuts off periodically for no specific reason 
and the controller restarts the fan by itself after about 
20 to 60 seconds, the cause could be a bad Air Flow 
switch. If the controller has a digital input assigned 
as a Proof of Air Flow input, try unconfiguring this 
digital input to see if these shutdowns continue. If 
not, adjust or replace the Air Flow switch to get it 
working.
Temperature Sensor and Setpoint Potentiometer 
Resistance Ranges
The T7770 or T7560A,B Wall Modules or the C7770A Air 
Temperature Sensor has the following specified calibration 
points, which are plotted in Fig. 40:
Temperature (°F)
Resistance Value (ohms)
98
11755
80
18478
70
24028
60
31525
42
52675
The T7770 Wall Module setpoint potentiometers have the 
following calibration points:
Temperature (°F)
Resistance Value (ohms)
85
1290
70
5500
55
9846
Fig. 40. Temperature sensor resistance plots.
Alarms
When an Excel 10 has an alarm condition, it reports it to the 
central node on the L
ON
W
ORKS
 Bus (typically, the Excel 10 
Zone Manager). See Table 12. Information contained in an 
alarm message is:
• Subnet Number:
L
ON
W
ORKS
 Bus subnet that contains the Excel 10 node 
that has the alarm condition. Subnet 1 is on the Zone 
Manager side of the router; Subnet 2 is on the other 
side.
• Node Number:
Excel 10 node that has the alarm condition (see 
Network Alarm).
• Alarm Type:
Specific alarm being issued. An Excel 10 can provide 
the alarm types listed in Table 12.
.
TEMPERATURE (DEGREES)
o
F
30
40
50
60
70
80
90
100
110
0
10
20
30
40
RESISTANCE (OHMS)
20K OHM AT 
77
o
F (25
o
C)
80K
70K
60K
50K
40K
30K
20K
10K
o
C
M11620
AIR TEMPERATURE SENSOR
10K OHM SETPOINT POT
RESISTANCE VALUES
Table 12. Excel 10 Alarms.
Name of alarm or error bit
Alarm type 
number
Meaning of alarm code or error bit
RETURN_TO_NORMAL
128U
Return to no alarm after being in an alarm condition. This code is added 
numerically to another alarm code to indicate that the alarm condition has 
returned to normal.
ALARM_NOTIFY_DISABLED
255U
The alarm reporting was turned off by DestManMode. No more alarms are 
reported until DestManMode turns on alarm reporting or on application restart.
NO_ALARM
0
No alarms presently detected.
INPUT_NV_FAILURE
1
One or more NV inputs have failed in receiving an update within their specified 
FAILURE_DETECT_TIME.
NODE_DISABLED
2
The control algorithm has stopped because the controller is in 
DISABLED_MODE, MANUAL or FACTORY_TEST mode. No more alarms are 
reported when the controller is in the DISABLED_MODE. Alarms continue to be 
reported if the controller is in the MANUAL or FACTORY_TEST mode.
SENSOR_FAILURE
3
One or more sensors have failed.
FROST_PROTECTION_ALARM
4
The space temperature is below the frost alarm limit 42.8°F (6°C) when the 
mode is FREEZE_PROTECT. The alarm condition remains until the temperature 
exceeds the alarm limit plus hysterisis.
INVALID_SET_POINT
5
One of the setpoints is not in the valid range.