Honeywell W7750A User Manual

Page of 116
EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER
74-2958—1
56
Fig. 45. LED and Bypass pushbutton operation.
STANDBY MODE (StatusOcySen)
The digital input for an occupancy sensor (usually a motion 
detector or possibly a time clock) provides the controller with a 
means to enter an energy-saving Standby mode whenever 
people are not in the room. Standby mode occurs when the 
scheduled occupancy is Occupied, and the occupancy sensor 
detects no people currently in the room (digital input contacts 
Closed means people are in the room, and contacts Open 
means the room is Unoccupied). When in Standby mode, the 
Excel 10 W7750 Controller uses the Standby Cooling Setpoint 
for cooling (CoolStbySpt), or the Standby Heating Setpoint for 
Heating (HeatStbySpt) as the Actual Space Temperature 
Setpoint. The occupancy sensor signal can also be a network 
input from another L
ON
W
ORKS
 Bus device, so that no physical 
sensor is required at the receiving W7750 Controller.
IMPORTANT
When the W7750 Controller is in Standby mode, the 
economizer minimum position setting is not 
observed. This means the fresh air dampers will go 
fully closed if there is no call for cooling.
CONTINUOUS UNOCCUPIED MODE
This mode is entered when a wall module is configured with a 
Bypass pushbutton that was pressed for four to seven 
seconds causing the wall module LED/LCD to blink. This 
mode can also be entered via a network command 
(ManualOcc set to Unoccupied). If the controller is in this 
mode, it reverts to the Unoccupied setpoints for temperature 
control, and the economizer does not observe its minimum 
position setting. The controller remains in this mode 
indefinitely until the Bypass pushbutton is pressed to exit the 
mode or a network command is sent to clear the mode. A 
configuration parameter is available to disable wall-module 
initiation of Continuous Unoccupied mode (OvrdType).
OCCUPANCY MODE AND MANUAL OVERRIDE ARBITRATION
The W7750 has multiple sources for occupancy schedule 
information and, therefore, it employs an arbitration scheme to 
determine the current actual mode. Time-of-day (TOD) 
schedule status comes from two sources, a configured digital 
input for OccTimeClock or the DestSchedOcc network input 
received from a central control. If the digital input source is 
configured, it has highest priority and determines the 
Occupancy mode. This digital input is either ON (shorted = 
occupied), OFF (open = unoccupied), or not active (not 
configured); otherwise, the status is determined by the 
DestSchedOcc input from the network source. The 
DestSchedOcc has three possible states, occupied, 
unoccupied or standby.
Manual Override Status can be derived from three sources 
and governed by two selectable arbitration schemes. The two 
schemes are:
Network Wins or Last-in Wins, as set in OvrdPriority.
The three sources of manual override status are:
DestManOcc - 
Has possible states: Occupied, 
Unoccupied, Bypass, Standby and Not 
Assigned (not active). This input source 
has the highest priority in determining 
manual override status for a Network 
Wins arbitration scheme, and in the 
event there is more than one source 
change at a time in the Last-in Wins 
arbitration scheme. Here, bypass 
initiates a self-timed bypass of the 
control unit and expires upon 
completion of the defined timed period. 
The controller then treats the bypass 
status of this input as Not Assigned until 
the next change in status.
M8483A
RESET
NOT ASSIGNED
(LED OFF)
PRESS FOR ONE
TO FOUR SECONDS
BYPASS OCCUPIED
(LED ON)
BYPASS
TIMEOUT
PRESS FOR FOUR 
TO SEVEN SECONDS
PRESS FOR LESS 
THAN ONE SECOND
UNOCCUPIED
(LED BLINK)
PRESS FOR LESS THAN ONE SECOND
PRESS FOR MORE THAN SEVEN SECONDS