Honeywell W7750A User Manual

Page of 116
EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER
7
74-2958—1
Control Application
W7750 systems in commercial buildings typically incorporate 
a packaged air handler system that delivers a constant 
volume of air at preconditioned temperatures to the zone 
being served. Each zone is usually serviced by a separate 
AHU; however, sometimes two or more AHUs service the 
same zone. Note that the W7750 is not designed to control 
Variable Air Volume (VAV) air handlers or Multi-Zone air 
handlers, where one air handler simultaneously controls the 
space temperature in many zones.
The W7750 can control staged or modulating heating and 
cooling coils, mixed air economizer dampers, and the system 
fan. Control of heat pump units, where the compressor(s) is 
used for both cooling and heating, is also provided. The zone 
the W7750 services can use a T7770 or T7650 for space 
temperature sensing and an L
ON
W
ORKS
 Bus network access 
for users. Fig. 2 shows a typical W7750 control application.
Fig. 2. Typical W7750 control application.
Control Provided
The W7750 Controller is designed to control a single air 
handler to maintain the units space temperature at the current 
setpoint. Heating and cooling control is provided for either 
staged or modulating equipment. Up to four stages of 
mechanical cooling and up to four stages of heating are 
allowed. Modulating outputs can be either floating type such 
as a Series 60 control, or Pulse Width Modulated (PWM 
W7750B,C only) control.
The economizer dampers can be controlled directly with 
floating or PWM outputs, or indirectly using a digital output as 
an enable/disable signal to a packaged economizer controller. 
The economizer enable function, which decides when to allow 
outdoor air to be used for free cooling, can be configured to 
one of ten strategies based on the inputs. For more details, 
see Appendix B—Sequences of Operation. When the 
economizer position is controlled from the W7750, the 
minimum position setting (for ventilation requirements) can be 
adjusted based on indoor air quality (IAQ) needs in the space. 
IAQ monitoring is provided through either a CO
2
 sensor or a 
digital input from a space-mounted IAQ limit switch.
For heat pump configurations, up to four compressors can be 
controlled, along with up to four stages of auxiliary heat, and a 
heat/cool change over valve. Including the supply fan, the 
combination of these items may not exceed eight outputs if a 
W7750B,C is used, or six outputs for a W7750A. (The eight 
outputs on the W7750C consist of five digital and three analog 
outputs.)
WINDOW CONTACT
OCCUPANCY
SENSOR
M
OA TEMP
FILTER
FAN
COOL
COIL
HEAT
COIL
DA TEMP
RA TEMP
EXCEL 10
W7750
CVAHU
T7770 OR T7560A,B
RETURN
AIR
DISCHARGE
AIR
OUTDOOR
AIR
CEILING
ROOF
-
+
M17488