Programming Manual - Basic & Applied Instruction Edition
38 Error Check Method and Error Code List
38.4 Error Code List and Action
31
FNC277
-F
NC2
79
79
Da
ta
Trans
fer 3
fer 3
32
FNC28
0-F
NC
289
289
H
igh-Speed
Process
ing 2
33
FNC2
90-
FNC299
FNC299
Ex
tensi
on Fi
le
le
Register C
ontrol
34
FN
C300-
FNC30
5
FX
3U
-C
F-
AD
P
35
SFC
•STL
Programming
36
Interrupt
Function
37
Sp
ec
ia
l D
evi
ce
38
E
rror Code
A
Ve
rsi
on U
p
Inform
ati
on
B
Ex
ecuti
on
T
imes
Operation error [M8067(D8067)]
0000
⎯
No error
6701
Continues
operation
•
No jump destination (pointer) for CJ or CALL
instruction
instruction
•
Label is undefined or out of P0 to P4095 due to
indexing
indexing
•
Label P63 is executed in CALL instruction; cannot be
used in CALL instruction as P63 is for jumping to
END instruction.
used in CALL instruction as P63 is for jumping to
END instruction.
This error occurs in the execution of operation. Review
the program and check the contents of the operands
used in applied instructions.
Even if the syntax or circuit design is correct, an
operation error may still occur.
For example:
"T500Z" itself is not an error. But if Z had a value of 100,
the timer T600 would be attempted to be accessed. This
would cause an operation error since there is no T600
device available.
the program and check the contents of the operands
used in applied instructions.
Even if the syntax or circuit design is correct, an
operation error may still occur.
For example:
"T500Z" itself is not an error. But if Z had a value of 100,
the timer T600 would be attempted to be accessed. This
would cause an operation error since there is no T600
device available.
6702
CALL instruction nesting level is 6 or more
6703
Interrupt nesting level is 3 or more
6704
FOR-NEXT instruction nesting level is 6 or more.
6705
Operand of applied instruction is inapplicable device.
6706
Device number range or data value for operand of
applied instruction exceeds limit.
applied instruction exceeds limit.
6707
File register is accessed without parameter setting of file
register.
register.
6708
FROM/TO instruction error
This error occurs in the execution of operation.
•
•
Review the program and check the contents of the
operands used in applied instructions.
operands used in applied instructions.
•
Verify that the specified buffer memories exist in the
counterpart equipment.
counterpart equipment.
•
Verify that extension cables are correctly connected.
6709
Other (e.g. improper branching)
This error occurs in the execution of operation. Review
the program and check the contents of the operands
used in applied instructions.
Even if the syntax or circuit design is correct, an
operation error may still occur.
For example:
"T500Z" itself is not an error. But if Z had a value of 100,
the timer T600 would be attempted to be accessed. This
would cause an operation error since there is no T600
device available.
the program and check the contents of the operands
used in applied instructions.
Even if the syntax or circuit design is correct, an
operation error may still occur.
For example:
"T500Z" itself is not an error. But if Z had a value of 100,
the timer T600 would be attempted to be accessed. This
would cause an operation error since there is no T600
device available.
6710
Mismatch among parameters
This error occurs when the same device is used within
the source and destination in a shift instruction, etc.
the source and destination in a shift instruction, etc.
6730
Incorrect sampling time (T
S
) (T
S
≤ 0)
<PID instruction is stopped.>
This error occurs in the parameter setting value or
operation data executing PID instruction.
Check the contents of the parameters.
This error occurs in the parameter setting value or
operation data executing PID instruction.
Check the contents of the parameters.
6732
Incompatible input filter constant (
α)
(
α < 0 or 100 ≤ α)
6733
Incompatible proportional gain (K
P
) (K
P
< 0)
6734
Incompatible integral time (T
I
) (T
I
< 0)
6735
Incompatible derivative gain (K
D
)
(K
D
< 0 or 201
≤ K
D
)
6736
Incompatible derivative time (T
D
) (T
D
< 0)
6740
Sampling time (T
S
)
≤ Scan time
<Auto tuning is continued.>
The operation is continued in the condition "sampling
time (T
The operation is continued in the condition "sampling
time (T
S
) = cyclic time (scan time)".
6742
Variation of measured value exceeds limit.
(UPV <
(UPV <
−32768 or +32767 < UPV)
<PID operation is continued.>
The operation is continued with each parameter set to the
maximum and minimum value.
The operation is continued with each parameter set to the
maximum and minimum value.
6743
Deviation exceeds limit.
(EV <
(EV <
−32768 or +32767 < EV)
6744
Integral result exceeds limit.
(Outside range from
(Outside range from
−32768 to +32767)
6745
Derivative value exceeds limit due to derivative gain
(K
(K
D
).
6746
Derivative result exceeds limit.
(Outside range from
(Outside range from
−32768 to +32767)
6747
PID operation result exceeds limit.
(Outside range from
(Outside range from
−32768 to +32767)
Error
code
PLC operation at
error occurrence
error occurrence
Contents of error
Action