2–Pump 20-Station Controllers 
Operation 
37 of 51 
Figure 20:  Alarm Log Screen 
 
 
To scroll up and down through the list, touch ▲ and ▼ at the bottom of the list. 
Silencing Alarms 
Whenever a new alarm occurs, your controller sounds the horn and turns on the strobe light at 
each central alarm.  
Touch Alarm Silence on the alarm message banner that appears when a new alarm occurs 
or press the physical push button included in the central alarm option. 
The horns and lights at the central alarms turn off. Your controller has separate, configurable 
settings for how long the horns should remain silent and how long the lights should remain 
off. (see “Setting U1p Alarm Duration” on page 19).  If the alarm condition still exists when 
either of these times elapses, the corresponding device (horn or lights) turn on again and the 
alarm message banner appears with a “Suppression/Silence Time Expired” message. If a new 
alarm occurs, both horns and lights turn on.  See page 436 for a list of alarms and their 
possible causes.