Servicing should only be performed by a Qualifi ed Service Agent
OPERATION AND SERVICE
Manifold Pressure Adjustment
The main gas regulators are found beneath the silver or black cap screws.   (Natural Gas 
valves have silver caps; Propane valves have a black caps). Remove the caps to access 
the outlet (manifold) pressure adjustment screw.  IMPORTANT: Ensure that the outlet 
pressure matches the manifold pressure that is listed on the water heater rating plate.  
Natural Gas valves are factory preset to 3.5 inches W.C.  The full rate outlet pressure 
• 
range is between 3 and 5 inches W.C.  
Propane (LP) valves are factory preset to 
• 
10.0 inches W.C.   The full rate outlet pressure 
range is between 8 and 12 inches W.C.  
Caution: Always test the manifold pressure at the outlet when the gas is flowing.
• 
Wiring Harness
TOP VIEW OF GAS VALVE
Main Gas
Regulators
(Outlet Pressure
Adjustment)
Lead Wires
(24-Volt Main Valve 
Solenoid Connections)
Figure 13
Main Valve Solenoid Connections
The figure above shows the two 24-volt main valve (MV) solenoid connections.  The two 
yellow wires from the 12-pin ignition board plug connect to these leads.