FIGURE 2.3 (B)  Minimum Slope 
 
 
 
2.4 
DRAFT 
 
Your  Sahara  stove’s  performance  will  be  optimised    if  it  is  installed  with  a  chimney  (flue)  system  that 
provides an adequate draft.  The draft is the force that moves air from the appliance up through the chimney 
and is predominantly affected by the height and diameter of the chimney, as well as the stack temperatures of 
the stove. If you test the draft using a pressure gauge, the reading should be between .05 - .07 inches of water 
column (w.c.) at a medium-high fire. A draft measure of less than .03" w.c. will cause operational difficulties 
while too much draft (greater than .10" w.c.) will result in over-firing of the stove. This can result in excessive 
operating  temperatures.  If  this  is  the  case,  a  manual  damper  may  be  installed  in  the  vertical  chimney  
connector to help reduce excessive draft. 
 
2.5 
OUTSIDE COMBUSTION AIR 
 
It is recommended to install 4’’ outside air intake  in the room where the stove is located or nearby. 
 
The following are signs that a fresh air kit may be required: 
 
• 
Your stove does not draw steadily, smoke rollouts occur, wood burns poorly, or back-draft occurs 
whether or not there is combustion present. 
 
• 
Existing fuel-fired equipment in the house, such as fireplaces or other heating appliances, smell, do 
not operate properly, suffer smoke rollouts when opened, or back-draft occurs whether or not there is 
combustion present.