Quadra-Fire SAPPHIRE-D-PMH User Manual

Page of 52
12
Quadra-Fire  •  Sapphire  •  7055-116  Rev. D  •  6/11
F.  Horizontal Termination
45° Elbow 
3 in. (76mm) Clearance from appliance 
corner to combustible wall
3 in. (76mm) 
Clearance from 
appliance corner to
combustible wall 
Wall Thimble/Heat Shield  
 
 
Wall Thimble/ 
Heat Shield
Wall Thimble Cover
Pipe Length
Pipe Length
Termination Cap
Center Line
90° Elbow
Type A - Up and Out Installation
Type B - Straight Out Installation
Type C - 45
°
 Elbow in Corner Installation
Wall Thimble 
Cover 
Pipe Length
Snorkel Kit
Wall Strap 14 in. 
(356mm) Wide
 
Minimum 6 in. 
(152mm)  of pipe 
through wall
Wall Thimble or Heat Shield
15-5/8 in. 
(397mm)
21 in. (533mm)
Center Line 
Figure 5.4   
Female Locking Lugs
Male Locking Lugs
Step 1. 
Determine the desired location of the appliance. Check 
to ensure that wall studs or roof rafters are not in the way 
when the venting system is attached. If this is the case, you 
may want to adjust the location of the appliance.
Figure 5.5
Step 2.  
Direct vent pipe is designed with a locking connection. To 
connect the venting system to the appliance flue outlet, a 
twist-lock adapter is built into the appliance at the factory.  
Wall thickness may vary.  Remember to include wall 
thickness in minimum clearances when figuring venting 
lengths for your installation needs.
Note:  Female ends of direct vent pipe/elbows are 
designed to slide straight onto the male ends of adjacent 
pipes by orienting the  pipe indentations so they match and 
slide into the  entry slots on the male ends, see
 Figure 5.5.  
Push the pipe sections completely together, then twist-lock 
one section clockwise approximately one-quarter turn, until 
the two sections are fully locked. The female locking lugs 
may not be visible from the outside. They may be located by 
examining the inside of the female ends.
Fire Risk.
Explosion Risk.
Combustion Fume Risk.
Use vent run supports per installation instructions.
Connect vent sections per installation instructions.
•  Maintain all clearances to combustibles.
•  Do NOT allow vent to sag below connection 
point to appliance.
 •  Maintain specifi ed slope (if required).
WARNING
Improper support may allow vent to sag or separate.
Fire Risk.
Exhaust Fume Risk.
Impaired Performance of Appliance.
WARNING
•  Ensure vent components are locked together correctly.
•  Pipe may separate if not properly joined.