CLEANING AND FLUSHING INSTRUCTIONS
INTERNAL CONTAMINANTS
The hydronic system must be internally cleaned and flushed 
after a new or replacement boiler has been installed to remove 
contaminants that may have accumulated during installation. 
This is doubly important when a replacement boiler is installed 
into an existing system where Stop Leak or other boiler additives 
have been used.
Failure  to  clean  and  flush  the  system  can  produce  acid 
concentrations  that  become  corrosive,  cause  gases  to  form 
that block water circulation or lead to formation of deposits on 
the boiler surfaces, any of which could result in damage to the 
system and circulator.
All hot water heating systems should be completely flushed with 
a grease removing solution to assure trouble-tree operation. 
Pipe joint compounds, soldering paste, grease on tubing and 
pipe all tend to contaminate a system.
Failure to flush contaminates from a system can cause solids 
to form on the inside of boiler exchangers, create excessive 
amounts  of  air  and  other  gases  to  block  circulation,  foul 
various system accessories and even deteriorate circulation 
seals and impellers.
It is recommended that after installation, the boiler and system 
when filled should include the proper percentage of cleaning 
solution related to approximate water volume of the system. Fire 
and circulate for about one hour and then flush clean with fresh 
water.  Commercial  grease  removing  solutions  are  available 
from your distributor.
HOT WATER SUPPLY BOILERS PREVENTIVE MAINTENANCE
For care of the HW water system please refer to the A. O. Smith 
Users Information Manual supplied with the Boiler.
PRE-TROUBLESHOOTING
Before any extensive troubleshooting, perform the following:
Ensure that:
 
–  Voltage (120 vac) is supplied to the appliance.
 
–  System control (tank temperature control, thermostat, etc.) 
is calling for appliance operation (call for heat).
 
–  Other contacts (switches) are closed (relay, low water cutoff, 
flow switch, coil protector, pressure switch, etc.).
 
–  Gas supply pressure is within the maximum and minimum 
operating ranges listed on the appliance rating plate/label.
 
–  Voltage (24 vac) is supplied by transformer.
 
–  Appliance is wired according to wiring diagram.
Note:  Cross  wiring  the  24  volt  circuit  of  the  relay  will  short  the 
transformer.
 
–  All wire terminals/connectors are firmly attached to valves, 
modules, switches, limit controls, etc.
 
–  For LP models only check for possible lockout condition of 
the the ignition module.