Toshiba RAV-SM566KRT-TR User Manual

Page of 112
CODE No. (DN) table (Please record the objective unit data at field)
Indoor unit capacity (CODE No. [11])
∗ Initial value of EEPROM installed on the supplied service P.C. board
DN
01
02
03
06
0C
0d
0F
10
11
12
13
14
1E
28
2A
2b
2E
32
60
69
Item
Filter sign lighting time
Dirty state of filter
Central control address
Heating suction temp shift
PRE-DEF indication selection
Cooling auto mode existence
Cooling only
Type
Indoor unit capacity (See below table)
Refrigerant line address
Indoor unit address
Group address
Temp difference of automatic cooling/
heating selecting control points
Auto restart
Option input selection (CN80)
Thermo output selection (T10 
ƒ
)
Input selection (T10 

)
Sensor selection
Timer set (Wired remote controller)
Louver selection of cooling
Memo
Be sure to set as 0008
At shipment
0001: 150 hour
0000: Standard
0099: Unfixed
0002: +2°C
0000: Standard
0001: No auto mode
Automatic selection by
cooling/heating
connected outdoor unit
0000: Heat pump
0008: High wall type
According to capacity type
0099: Unfixed
0099: Unfixed
0099: Unfixed
0003: 3deg (Ts ± 1.5)
0001: Provided
0002: External emergency input
0000: Thermo ON
0000: Operation input
0000: Available
0000: Available
0000: Standard
SET DATA
 0001∗
0009
0012
Model
Invalid
56
80
FILE NO. SVM-12004
– 