Trane 2TTB3 User Manual

Page of 8
4
18-AC56D1-1
Installer’s Guide
E. ELECTRICAL CONNECTIONS
WARNING
!
When installing or servicing this equipment, ALWAYS
exercise basic safety precautions to avoid the possibility of
electric shock.
1. Power wiring and grounding of equipment must comply
with local codes.
2. Power supply must agree with equipment nameplate.
3. Install a separate disconnect switch at the outdoor unit.
4. Ground the outdoor unit per local code requirements.
5. Provide flexible electrical conduit whenever vibration
transmission may create a noise problem within the
structure.
6. The use of color coded low voltage wire is recommended
to simplify connections between the outdoor unit, the
thermostat and the indoor unit.
Table 1 — NEC Class II Control Wiring
24 VOLTS
WIRE SIZE
MAX. WIRE LENGTH
18 AWG
150 FT
16 AWG
225 FT.
14 AWG
300 FT.
7. Table 1 defines maximum total length of low voltage
wiring from outdoor unit, to indoor unit, and to thermostat.
8. Mount the indoor thermostat in accordance with instruc-
tion included with the thermostat.  Wire per appropriate
hook-up diagram (included in these instructions).
F. COMPRESSOR START-UP
After all electrical wiring is complete, SET THE THERMO-
STAT SYSTEM SWITCH IN THE OFF POSITION SO
COMPRESSOR WILL NOT RUN, and apply power by
closing the system main disconnect switch.  This will activate
the compressor sump heat (where used).  Do not change the
Thermostat System Switch until power has been applied for
one (1) hour. Following this procedure will prevent potential
compressor overload trip at the initial start-up.
INDOOR THERMOSTAT
SWITCH SETTING
1
1
Fan Switch
TO CHECK
Off
Cool
Heat
Auto
On
COMPONENT OPERATION
Indoor
Outdoor
Compressor
3
 Comp.
Furnace
Blower
Fan
Runs
Sump
Heat
Runs
Runs
Heater
Comes On
Step
No.
CHECKOUT PROCEDURE WITH MAIN POWER DISCONNECTS CLOSED (ON)
1
Also set thermostat dial to call for cooling or heating as necessary.
2
Check only necessary if heating unit is used for indoor section and wiring has been disturbed during installation of cooling equipment.
3
When applicable.
1
Sump Heat
X
X
X
2
Indoor Fan Operation
X
X
X
X
3
Cooling Operation
X
X
X
X
X
X
4
Checking Performance
X
X
X
X
X
X
& Charge
USE CHARTS ATTACHED TO O.D. UNIT
5
Heating 
2
X
X
X
X
X
6
Inform owner on how to operate system and what to expect of it. At the same time deliver Owner’s Use and Care Booklet.
G. OPERATIONAL AND
CHECKOUT PROCEDURES
Final phases of this installation are the unit Operational and
Checkout Procedures which are found in this instruction (see
table below and pages 6 and 8). To obtain proper perfor-
mance, all units must be operated and charge adjustments
made in accordance with procedures found on page 6 and in
the Service Facts.
H. SEACOAST SHIELD
Units installed within one mile of salt water, including
seacoasts and inland waterways, require the addition of
BAYSEAC001 (Seacoast Kit) at the time of installation.
IMPORTANT:
See Limited Warranty information in Use and Care Manual.
I. TROUBLESHOOTING
REFRIGERANT CIRCUIT
Liquid Pressure Too High
Liquid Pressure Too Low
Suction Pressure Too High
Suction Pressure Too Low
Liquid Refrig. Floodback TXV System
I.D. Coil Frosting
Compressor Runs Inadequate or No Cooling
ELECTRICAL
Compressor & O.D. Fan Do Not Start
Compressor Will Not Start But O.D. Fan Runs
O.D. Fan Won’t Start
Compressor Hums But Won’t Start
Compressor Cycles on IOL
I.D. Blower Won’t Start
SYSTEM FAULTS
P - Primary Causes      S - Secondary Causes
P
P
P
S
S
P
S
S
S
S
S
P
S
S
S
P
P
P
S
S
S
S
S
S
S
P
P
P
S
P
P
S
S
S
P
P
P
P
P
P
P
P
P
P
S
S
S
P
P
P
P
P
S
P
S
P
S
S
S
S
S
S
S
P
P
P
P
P
S
P
P
POW
ER SUPPLY
HIGH
 VO
LTAG
E W
IR
IN
G
CO
MPR. IO
L
RU
N CAPACITOR
STAR
T CAPACITOR
START R
ELAY
CO
NTAC
TO
R CO
NTACTS
LO
W
 VO
LTAGE W
IR
IN
G
CO
NTR
O
L TRANSFO
RM
ER
CON
TAC
TOR
 C
O
IL
LOW
 VO
LTAGE FUSE
STU
CK C
O
M
PRESSO
R
INE
FFICI
ENT CO
M
PRESSO
R
REFRIG
ERANT U
NDERC
HARG
E
REFR
IG
ERAN
T OVERC
HA
RGE
EXCE
SS
IVE EVAP. LO
AD
NO
NCO
NDE
NSAB
LES
RESTRICTED
 O.D
. AIR
FLO
W
O.D
. AIR REC
IR
CULATION
TXV S
TU
CK O
PEN
SUPERH
EA
T
RESTRICTED I.D.
 AIRFLO
W
REF. C
IRC
UIT RESTRICTIO
NS
O
.D
. FA
N SPEED
 SW
ITCH
TROUBLESHOOTING CHART — WHAT TO CHECK