Piping
19
6.7.1 Connecting Methods—One-Shot Couplings for Pre-Charged Refrigerant Option
Liebert XDRs with the pre-charged option are equipped with one-shot couplings on the supply and 
return fittings. These contain a charge of R-134a refrigerant under pressure within the module. This 
charge must not be vented.
Do not remove the pipe caps or plugs before the module is ready for connection to Liebert XD Piping. 
Do not disconnect one-shot Liebert XD Flex Pipes after they have been connected.
The assembly and connection means used for piping in the Liebert XD system are the same as those 
used in conventional refrigeration systems. Observe all standard practices during installation and 
startup to prevent damage and contamination.
Both supply and return fittings may be supplied with optional, one-shot couplings. These fittings con-
tain pressurized R-134a refrigerant inside the Liebert XDR.
If the module includes the optional, factory-installed, one-shot style couplings, proceed with 6.7.2 - 
Figure 17 Piping location and connection sizes—modules with pre-charged modules
!
CAUTION
Risk of sudden refrigerant discharge. Can cause loss of charge and minor injury.
If the optional pre-charged option is chosen, the Liebert XDR is shipped with a full charge of 
R-134a refrigerant under pressure. Do not remove the pipe caps or plugs before the module is 
ready for connection to Liebert XD Piping.
Supply and return fittings on the pre-charged Liebert XDR modules are one-shot couplings. 
Do not disconnect one-shot couplings after they have been connected. Disconnection will 
release pressurized R-134a refrigerant from the Liebert XDR.
5-7/8"
(149mm)
1-1/2"
(38mm)
2-1/8" 
(54mm)
1-1/8" 
(29mm)
6-1/2" 
(165mm)
TOP VIEW
(Rear of Cabinet)
Refrigerant  
Supply Line
Schrader Valve
(Do Not Vent)
23-1/2" (597mm)
Refrigerant  
Return Line
1-5/16" 
(33mm)