4. Shaded RPMs require Class II blower.
TABLE 31: FAN PERFORMANCE - 30 TON 
1,
 
2
 
A
IRFLOW 
(CFM)
A
VAILABLE 
E
XTERNAL 
S
TATIC 
P
RESSURE 
(IWG)
0.2
0.4
0.6
0.8
1.0
RPM
BHP
3
RPM
BHP
3
RPM
BHP
3
RPM
BHP
3
RPM
BHP
3
6000
405
1.3
450
1.6
494
2.0
535
2.3
575
2.7
7000
444
1.9
485
2.3
524
2.7
562
3.0
599
3.4
8000
483
2.6
519
2.9
555
3.3
589
3.7
623
4.2
9000
520
3.5
554
3.9
586
4.3
618
4.7
649
5.2
10000
558
4.5
588
4.8
618
5.2
647
5.7
676
6.2
11000
603
5.7
629
6.2
656
6.7
683
7.2
709
7.7
12000
647
7.0
671
7.5
695
8.1
718
8.6
742
9.2
13000
687
8.9
709
9.3
731
9.9
753
10.4
776
10.9
14000
728
10.7
748
11.2
768
11.6
789
12.2
809
12.7
15000
767
12.7
786
13.2
805
13.8
825
14.4
845
15.0
A
IRFLOW 
(CFM)
A
VAILABLE 
E
XTERNAL 
S
TATIC 
P
RESSURE 
(IWG)
1.2
1.4
1.6
1.8
2.0
RPM
BHP
3
RPM
BHP
3
RPM
BHP
3
RPM
BHP
3
RPM
BHP
3
6000
612
3.1
649
3.5
683
3.9
717
4.3
748
4.7
7000
634
3.8
668
4.3
701
4.7
733
5.1
763
5.6
8000
655
4.6
687
5.1
719
5.5
749
6.0
779
6.5
9000
680
5.6
710
6.1
739
6.6
768
7.2
796
7.7
10000
704
6.7
732
7.2
760
7.7
787
8.3
813
8.9
11000
735
8.2
761
8.7
787
9.3
812
9.8
837
10.4
12000
766
9.7
790
10.3
814
10.8
837
11.4
861
12.0
13000
798
11.5
820
12.1
843
12.7
865
13.3
887
13.9
14000
830
13.3
851
13.9
872
14.6
893
15.2
914
15.9
15000
864
15.6
884
16.3
904
16.9
923
17.6
943
18.3
A
IRFLOW 
(CFM)
A
VAILABLE 
E
XTERNAL 
S
TATIC 
P
RESSURE 
(IWG)
2.2
2.4
2.6
2.8
3.0
RPM
BHP
3
RPM
BHP
3
RPM
BHP
3
RPM
BHP
3
RPM
BHP
3
6000
779
5.1
808
5.5
837
6.0
864
6.4
890
6.9
7000
793
6.1
822
6.6
850
7.0
877
7.5
903
8.1
8000
807
7.0
836
7.6
863
8.1
890
8.6
916
9.2
9000
823
8.3
850
8.8
877
9.4
902
10.0
928
10.6
10000
839
9.5
865
10.1
890
10.7
915
11.3
940
12.0
11000
862
11.0
886
11.6
910
12.2
934
12.9
957
13.5
12000
884
12.5
907
13.2
930
13.8
953
14.4
975
15.0
13000
909
14.6
931
15.2
953
15.9
975
16.5
996
17.2
14000
935
16.6
956
17.3
976
18.0
997
18.7
1017
19.4
15000
963
18.9
982
19.6
1002
20.4
1021
21.1
1040
21.8
A
IRFLOW 
(CFM)
A
VAILABLE 
E
XTERNAL 
S
TATIC 
P
RESSURE 
(IWG)
3.2
3.4
3.6
3.8
4.0
RPM
BHP
3
RPM
BHP
3
RPM
BHP
3
RPM
BHP
3
RPM
BHP
3
6000
916
7.4
940
7.9
964
8.3
988
8.8
1011
9.3
7000
928
8.6
953
9.1
977
9.6
1000
10.1
1023
10.7
8000
941
9.8
965
10.3
989
10.9
1013
11.5
1035
12.0
9000
952
11.2
976
11.8
1000
12.4
1023
13.0
1045
13.6
10000
964
12.6
987
13.2
1010
13.9
1033
14.5
1055
15.1
11000
981
14.1
1003
14.8
1025
15.5
1047
16.1
1069
16.8
12000
997
15.7
1019
16.4
1040
17.1
1061
17.8
1082
18.5
13000
1017
17.9
1038
18.6
1058
19.4
1078
20.1
1097
20.8
14000
1037
20.2
1056
20.9
1076
21.6
1094
22.4
1113
23.1
15000
1059
22.6
1078
23.3
1097
24.1
1115
24.9
1134
25.7
1.
Fan performance is based on wet evaporator coils, clean 2” throwaway filters and system/cabinet effects at standard air density and 0 feet elevation.
2.
3.
BHP includes drive losses.