Specifications and Performance
INSTALLATION & OPERATING INSTRUCTIONS & PARTS MANUAL
MODELS:
E3606-1325HFD, E3609-1325HFD
E3806-1325HFD, E3809-1325HFD
E4206-1325HFD, E4209-1325HFD
E4806-1325HFD, E4809-1325HFD
E6006-2325HFD, E6009-2325HFD
READ CAREFULLY BEFORE ATTEMPTING TO ASSEMBLE, INSTALL, OPERATE, OR MAINTAIN THE PRODUCT DESCRIBED.
PROTECT YOURSELF AND OTHERS BY OBSERVING ALL SAFETY INFORMATION. FAILURE TO COMPLY WITH INSTRUCTIONS
COULD RESULT IN PERSONAL INJURY AND/OR PROPERTY DAMAGE!
RETAIN INSTRUCTIONS FOR FUTURE REFERENCE.
Air  curtains  produce  a  wall  of  continuously  flowing  air
that  acts  as  a  thermal  barrier  against  outside  air  and
provides  protection  against  insects,  dust,  odor,  fumes
and other contaminant’s. Maintains interior conditioned
temperature  by  preventing  heated  or  cooled  air  from
escaping through open doorways. 
Heated  air  curtains  are  engineered  to  treat  incoming
cold air at customers’ entrance areas. Used over front
door entrances, heated air curtains supplement existing
heat to prevent infiltration of colder outside air. Heated
units  are  not  recommended  for  areas  subject  to  high
winds.
Figure 2 Dimensions
Note that all dimensions are the same on all environmental
series units. Model number indicates width of unit.
(Example: E4800 indicates a 48” wide unit.)
MODEL 
NUMBER
E3606-1325HFD
E3609-1325HFD
E4206-1325HFD
E4209-1325HFD
E4806-1325HFD
E4809-1325HFD
E6006-2325HFD
E6009-2325HFD
HEATER
VOLTAGE
208/3
208/3
208/3
208/3
208/3
208/3
208/3
208/3
MOTOR
VOLTAGE
208/3
208/3
208/3
208/3
208/3
208/3
208/3
208/3
HEATER
WATTS
6000
9000
6000
9000
6000
9000
6000
9000
HEATER
BTU/HR
HEATER
AMPS
20,478
30,717
20,478
30,717
20,478
30,717
20,478
30,717
16.7
25.0
16.7
25.0
16.7
25.0
16.7
25.0
CFM AT NOZZLE
(HI/LOW)
2025
2025
2360
2360
2700
2700
3375
3375
MOTOR
SIZE
1/4HP
1/4HP
1/4HP
1/4HP
1/4HP
1/4HP
1/4HP
1/4HP
Heated
Air Curtains
Note: For multiple unit installations, recommended spacing between units should be a minimum of 3-inches and a maximum of 6-inches.
Unit is allowed to extend beyond doorway width. Each unit must have individual power supply.
Description
REFER TO INDIVIDUAL MODEL NUMBERS
FOR UNIT WIDTH
11
7
/
8
15
3
/
4
12
1
/
2
Figure 1