5. ACtUAtOR CONNECtIONS
  Electrical and/or pneumatic connections to damper 
actuators should be made in accordance with wiring and 
piping diagrams developed in compliance with applicable 
codes, ordinances and regulations (see Electrical 
Guidelines).
6. CONNECtION AND OPERAtION OF 
tEMPERAtURE RESPONSE DEVICES (Fusible 
Link, RRL OPtION, OCI OPtION, tOR OPtION, 
and PRV OPtION)
RRL - Dampers will be supplied with a fusible link 
temperature response device, as a standard. An optional 
thermostat type temperature response device may have 
been installed. The device is a RRL (resetable link device), 
which only incorporates one thermostat and therefore the 
damper remains closed as soon as its sensor temperature 
is reached. The RRL does not contain blade indication 
switches. Refer to Fig. 4 on page 5 for wiring of the RRL 
thermostat.
OCI - The OCI (open or closed indicator) option contains 
a single pole, double throw switch used to indicate the 
damper blade position. The switch provides a positive open 
or closed signal when used in conjunction with remote 
indicator lights. Refer to Fig. 5 on page 5 for wiring of the 
OCI option.
tOR - The TOR (temperature override device) option 
incorporates two thermostats with fixed settings (usually 
165°F and 350°F). The primary sensor (the sensor with the 
lower temperature setting) can be bypassed by an external 
electrical signal allowing the damper to reopen until the 
temperature reaches the setting of the secondary sensor 
(the sensor with the higher temperature setting). When 
the temperature of the secondary sensor is exceeded the 
damper closes and remains closed thereafter (Fig. 6)
The TOR assembly also contains a single pole, double 
throw switch used to indicate damper blade position. The 
switch provides a positive open or closed signal when used 
in conjunction with remote indicator lights. See page 6, Fig. 
6 for wiring of the TOR thermostats and indicator switches.
If either the TOR or the RRL is ordered with a pneumatic 
actuator, an EP switch is required with an appropriate 
electric power circuit to allow the electric thermostat to 
control the pneumatic actuator.
PRV - The PRV (pneumatic relief valve) option is heat 
responsive device used with pneumatic actuators. This 
can be used in place of EP switch where a RRL is used.  
The PRV activates when temperature in excess of the 
temperature of the fusible link are detected. When the 
fusible link melts, air from the actuator is exhausted to 
close the dampers. Pneumatic actuators are to be piped 
per local code.
Fig. 3
L1
M
L2
ELECTRIC DAMPER
ACTUATOR OR PNEUMATIC
SOLENOID  VALVE
PRIMARY TEMP
SENSOR
ELECTRICAL CAPACITY = 10 AMP  @ 120 / 240 VAC
BLACK
ORANGE
P
NC
BLACK
WHITE/RED
Fig. 4
RRL Wiring
RAtINGS  (Fig. 4 & 5) 
 
  Integral Switch type:   Single Pole, double throw
 
          Electrical:    10 Amps, 
1
/
3
 hp, 120 or 240 Vac
 
   
1
/
2
 Amp, 125 Vdc; 
1
/
4
 Amp 250 Vdc 
 
   5 Amps, 120 Vac “L” (lamp load)
 
   1.0 Amps, 24 Vac
 
   1.5 Amps, 24 Vdc
 
temperature Limit:   165° F (standard primary sensor)
 
  212° F (optional primary sensor)
 
  250° F (secondary sensor)
 
  350º F ( secondary sensor)
-