Fire alarm systems 
Analog photoelectric 
smoke detector 
4301 
•  Constant sensitivity / Service signal at a fixed level of contamination 
•  New advanced algorithms and functions and yet compatible with older EBL systems 
General 
The photoelectric (optical) smoke detector 
has a low profile design, 
unleaded 
soldering
 and the latest IC technology, 
which will secure the highest reliability 
possible.  In the detection chamber is a high-
efficient optical system consisting of an 
LED and a photodiode with two lenses.  
Scattered light (i.e. reflection of infrared 
light) is used to detect smoke.  The smoke 
enters the detection chamber through an 
insect filter and an optical labyrinth.  This 
construction not only improves the smoke 
inflow but it also causes steam, fog, etc. to 
condense into moisture on its surfaces, to 
prevent false (nuisance) alarms.   
The detector is supplied with two LEDs that 
will light when the detector goes into alarm.  
The detector is plugged in the analog base 
3312x / 4313.  The COM loop is connected 
to the base, which also has terminals for an 
external LED, e.g. 2218. The detector is 
intended for indoor use in dry premises and 
in the systems EBL512 / 128 / 1000 / 2000 
depending on the detector mode. 
Constant sensitivity 
The detector maintains a constant sensitivity 
regardless of its contamination.  A service 
signal will be given when the detector has 
reached a service level.   
Address / Detector mode 
The address setting tool 3314 is used to set 
the detector's COM loop address and the 
detector mode NORMAL, 2330 or 2312 See 
Planning Instructions for the system 
respectively for more information about the 
modes and functions. 
•  NORMAL mode (analog):  Detector 
4301 is used in the systems EBL512 
(SW version > 2.0) and EBL128, also as 
a spare part for the detector 3304 in 
NORMAL mode. 
•  2330 mode (conventional):  Detector 
4301 is used in the systems EBL512/ 
1000/2000 as a spare part for the 
detector 3304 in 2330 mode. 
•  2312 mode (analog):  Detector 4301 is 
used in the systems EBL512/1000/2000 
as a spare part for the detector 3304 in 
2312 mode. 
The different modes have different functions 
and features, e.g. in the 2330 mode, the 
detector does the fire judgement but in the 
NORMAL and 2312 modes this is done in 
the c.i.e.  The detector is prepared for an 
"Advanced mode" to be used in conjunction 
with future EBLxxx SW versions. 
AI function 
In the 2330 mode is the AI function used, 
i.e.: 
•  Variable delay function, i.e. the delay 
time before an alarm is influenced by 
temporary smoke obscuration changes.