Panasonic Electric Works Fire & Security Technology Europe AB 
 
Jungmansgatan 12, SE-211 19 Malmö, Sweden 
Tel: +46 (0)40 697 70 00 • Fax: +46 (0)40 697 70 99 
info-fste@eu.pewg.panasonic.com • www.panasonic-fire-security.com 
Fire alarm systems 
Analog 
multi detector 
4300 
•  Constant sensitivity / Service signal at a fixed level of contamination 
•  New advanced algorithms and functions and yet compatible with older EBL systems 
General 
The multi detector contains one photo-
electric (optical) smoke detector and one 
heat detector within the low profile housing.  
The latest IC technology will secure the 
highest reliability possible. It has 
unleaded 
soldering
.  In the smoke detection chamber 
is a high-efficient optical system consisting 
of an LED and a photodiode with two 
lenses.  Scattered light (i.e. reflection of 
infrared light) is used to detect smoke.  The 
smoke enters the detection chamber through 
an insect filter and an optical labyrinth.  This 
construction not only improves the smoke 
inflow, it also causes steam, fog, etc. to 
condense into moisture on its surfaces, to 
prevent false (nuisance) alarms.   
The  heat sensing element is a thermistor.  
The detector is supplied with two LEDs that 
will light when the detector goes into alarm.  
The detector is plugged in the analog base 
3312x / 4313.  The COM loop is connected 
to the base, which also has terminals for an 
external LED, e.g. 2218. The detector is 
intended for indoor use in dry premises and 
in the systems EBL512 / 128 / 1000 / 2000 
depending on the detector mode. 
Constant sensitivity 
The detector maintains a constant sensitivity 
regardless of its contamination.  A service 
signal will be given when the detector has 
reached a service level.   
Address / Detector mode 
The address setting tool 3314 is used to set 
the detector's COM loop address and the 
detector mode NORMAL, 2330 or 2312. 
See Planning Instructions for the system 
respectively for more information about the 
modes and functions. 
•  NORMAL mode (analog):  Detector 
4300 is used in the systems EBL512 
(SW version > 2.0) and EBL128, also as 
a spare part for the detector 3316 in 
NORMAL mode. 
•  2330 mode (conventional):  Detector 
4300 is used in the systems EBL512 / 
1000 / 2000 as the best substitute for the 
detectors 2316 & 2317 + base 2330. 
•  2312 mode (analog):  Not used for 4300.  
The different modes have different functions 
and features, e.g. in the 2330 mode, the 
detector does the fire judgement but in the 
NORMAL mode this is done in the c.i.e.  
The detector is prepared for an "Advanced 
mode" to be used in conjunction with future 
EBLxxx SW versions. 
AI function 
In the 2330 mode is the AI function used, 
i.e.: 
•  Combined heat and smoke sensing will 
guarantee reliable and accurate fire alarm 
detection. 
•  Variable delay function, i.e. the delay 
time before an alarm is influenced by 
temporary temperature and/or smoke 
obscuration changes.