Desa CGP16RA User Manual

Page of 32
8
101827
AIR FOR
COMBUSTION
AND
VENTILATION
Continued
VENTILATION AIR 
(Continued)
Ventilation Air From Outdoors
Provide extra fresh air by using ventilation grills or ducts. You must provide
two permanent openings: one within 12" of the ceiling and one within 12" of
the floor. Connect these items directly to the outdoors or spaces open to the
outdoors. These spaces include attics and crawl spaces. Follow the National
Fuel Gas Code NFPA 54/ANSI Z223.1, Section 5.3, Air for Combustion and
Ventilation
 for required size of ventilation grills or ducts.
IMPORTANT:
 
Do not provide openings for inlet or outlet air into attic if attic
has a thermostat-controlled power vent. Heated air entering the attic will
activate the power vent.
Figure 3 - Ventilation Air from Outdoors
Outlet
Air
Ventilated
Attic 
Outlet
Air
Inlet
Air
Inlet Air
Ventilated 
Crawl Space
To 
Crawl
Space
To Attic