Mitsubishi Electronics PAC-YG63MCA User Manual

Page of 16
7
7-2. Connecting the Power and M-NET Transmission Lines
 
 
FG
 
M-NET
S / B / 
A
 (M1)
 (M2)
U
U
R
V+/V-/FG 
CN02 
A/B/S 
Tightening torque for terminal screws: 1 N·m
Connect the M-NET transmission line of this device to a power 
supply unit (PAC-SC50KUA) for the M-NET transmission line 
or an outdoor unit (either a centralized control line or indoor 
control line can be connected).
* Only the M-NET circuitry of this device receives the power from the 
M-NET transmission line. The power consumption factor is "1/4" 
(equivalent to one ME Remote Controller).
Figure 7-1 Example of Connecting the Power Line and M-NET Transmission Line
AI controller
Field 
Connections
(example)
Fuse
Varistor
Arrester
Noise
Filter
24 VDC 
Power 
source
AC power Line
* Functional 
ground
Varistor
 Caution:
• Use a power line and M-NET transmission line that satisfy the specifications described in "6-1. Parts Purchased Separately". 
• Attach a circuit comprising the following components to the supply primary side of the 24 VDC power supply. 
 (1) Varistor, (2) Arrester, (3) Noise filter, (4) Fuse
• It is important to pay attention to the polarity when connecting to the 24 VDC power supply terminal block. 
Connecting the positive and negative in the reverse order will cause a failure. 
• Fix the power line and M-NET transmission line in place on the outside to ensure that the terminal block is not affected by 
any external force. 
Not securely connecting and fixing the wires in place may cause heat generation and fire.
• Make sure that the copper wiring is not short-circuiting the plates (cover, lower case) or neighboring wires.
Cover the shielded line of the M-NET transmission line with materials such as vinyl tape and prevent short-circuiting with the 
plates.
Note: 
• If the M-NET transmission line of this device is connected to an M-NET indoor control line and the outdoor unit is down 
because, for example, the power supply is interrupted for servicing or there is a failure, the AI controller cannot be set and 
monitored from the system controller.
• Be sure to ground this device, PAC-SC50KUA and 24 VDC Power source. 
Measurement accuracy may be affected if devices are not grounded.