CellPower VRLA battery CP1,2-12 Leaflet

Product codes
CP1,2-12
Page of 2
 
 
 
WWW.CELLPOWERBATTERIES.COM  
SALES@CELLPOWERBATTERIES.COM
  
PAGE 1 OF 2
 
 
 
 
Battery for multi purpose use 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
Constant Current Discharge Characteristics (A, 20°C) 
F.V/TIME 5min  10min 15min 30min 60min  3h 
5h 
10h  20h 
9.60V 
5.00  
3.20  
2.50  
1.45  
0.82 
0.33  
0.22  
0.12  
0.06  
10.2V 
4.75  
3.04  
2.40  
1.39  
0.79  
0.33  
0.22  
0.12  
0.06  
10.8V 
4.47  
2.86  
2.28  
1.32  
0.75  
0.32  
0.21  
0.12  
0.06  
 
Constant Power Discharge Characteristics (Watt, 20°C)
 
 
F.V/TIME 5min  10min 15min 30min 60min  3h 
5h 
10h  20h 
9.60V 
55.8  
36.1  
28.5  
16.6  
9.50 
3.92  
2.63  
1.44  
0.72  
10.2V 
53.0 
34.3 
27.4  
15.9  
9.15  
3.92  
2.63 
1.44  
0.72  
10.8V 
49.9  
32.3  
26.0  
15.1  
8.69  
3.80  
2.51 
1.44 
0.72  
 
Nominal voltage 
 12 
DC 
Nominal Capacity 
(20HR,20°C): 
 
1,2 Ah 
Internal resistance 
 
Approx. 95 m  
Maximum charging current 
 
0,3 A 
Maximum discharge current 
 
18 A (5 sec.) 
Operating temperature 
range 
 
-20°C  50°C 
Float use/ cycle use 
 
13,6 - 13,8V/ 14,5 – 14,9V 
Expected life  (20°C)  
 
3 – 5 years in float charge 
Standard terminal 
 
Faston 4,8 mm
 
Housing material 
 
ABS FR GLASS HB 
length 
 97 
mm 
width 
 43 
mm 
Dimensions 
height 
 
58 mm  (
±1
 mm) 
Approx. Weight 
 
0.61 kg 
Packing 
 
20 pcs/box 
CP 1,2-12 
 
Typical applications: 
• 
Alarm devices 
• 
Measuring equipment 
• 
Emergency lightning 
• 
Medical equipment 
• 
Telecommunication systems 
• 
UPS systems 
• 
Toys 
• 
Domestic applications. 
• 
Valve Regulated Maintenance Free 
 
• 
High current drain grid being 
resistant to corrosion  
by virtue of a lead-calcium alloy
 
• Absorbent Glassmat Technology 
(AGM)
 
• Classified as non- spillable and Non 
Dangerous goods by IATA, FAA, 
ADR, IMDG 
• Can be discharged or stored in any 
position without leakage 
• Cannot be charged while the 
terminal is downward