Tripp Lite SmartOnline 200-240V 10kVA 9kW On-Line Double-Conversion UPS, Extended Run, SNMP, Webcard, 6U Rack/Tower, USB, DB9 Serial, Bypass Switch SU10000RT3U User Manual

Product codes
SU10000RT3U
Page of 7
Output voltage
regulation (line mode)
+/- 2%
Output voltage
regulation (Economy
line mode)
+/- 10%
Output voltage
regulation (Battery
mode)
+/- 2%
Built-in UPS output
receptacles
4 L6-20R outlet(s); 2 L6-30R outlet(s)
Output circuit breaker
20A double-pole (x2) protects 2 L6-20R outlets each, 30A double-pole (x2) protects 1 L6-30R outlets each
Basic PDU options
outlets)
Metered PDU options
Switched PDU options
 (0U / 4 C19, 24
C13 outlets); 
 (0U / 4 C19, 24 C13 outlets)
Output AC waveform
(AC mode)
Sine wave
Output AC waveform
(battery mode)
Sine wave
INPUT
Rated input current (at
maximum load)
46.7A (200V), 44.9 (208V), 42.4 (220V), 40.6 (230V), 38.9 (240V)
Nominal Input
Voltage(s) Supported
200V AC; 208V AC; 220V AC; 240V AC
UPS input connection
type
Hardwire
UPS input connection
description
3 wire single phase input (L1, L2, G)
Recommended
Electrical Service
50A 208/240V
BATTERY
Full load runtime
(minutes)
4 min. (8000w)
Half load runtime
(minutes)
10 min. (4000w)
Expandable battery
runtime
Supports extended runtime with optional external battery packs
External battery pack
compatibility
DC system voltage
240V DC
Battery recharge rate
(included batteries)
Less than 8 hours from 10% to 90%
Battery replacement
description
Hot-swappable, user replaceable batteries
VOLTAGE REGULATION