Phihong POE576U-8HPN User Manual

Page of 3
POE576U Characteristics 
 
WWW.PHIHONG.COM
INPUT: 
AC Input  
Voltage Range
 
90 to 264VAC
  
Input Frequency 47-63Hz 
Input Current: 
9A (RMS) maximum for 90VAC 
4.5A (RMS) maximum for 230VAC 
Leakage Current: 3.5mA maximum @ 264VAC 60Hz  
AC Inrush Current: 
30A (RMS) maximum for 115VAC 
60A (RMS) maximum for 230VAC 
 
OUTPUT: 
Total Output Power 
33.6W per port 
Total Power 269W (8 ports) -538W (16 ports)  
 
Ripple and Regulation 
100mV maximum 
 
Efficiency 
75% (typical) at maximum load, and 120VAC 60Hz 
 
Hold-up Time 
16mS min. 120VAC and maximum load 
 
Transient O/P Voltage Protection 
60V maximum at switch on and off at any AC line Phase 
 
Turn-On Delay Time 
20 sec maximum at maximum load, and 120VAC 60Hz, 
60Hz 
 
ENVIRONMENTAL: 
Temperature 
Operation 
 
0 to +40°C 
Non-operation 
 
-25 to +65°C
 
 
Humidity 
Operation 
 
5 to 90% 
Non-Operation   
5 to 90% 
 
EMC 
EN55022 Class A, FCC Class A with UTP cabling 
EN55022 Class B, FCC Class B with FTP cabling 
 
Isolation Test 
Primary to Secondary: 4242VDC for 1 minute  
Primary to Ground: 2121VDC for 1 minute 
Secondary to Ground: 2121VDC for 1 minute 
 
Immunity EN50082-1 
ESD: 
 
EN61000-4-2.  Level 3 
RS: 
 
EN61000-4-3.  Level 2 
EFT: 
 
EN61000-4-4.  Level 2 
Surge:   
EN61000-4-5.  Level 3 
CS: 
 
EN61000-4-6.  Level 2 
Voltage Dips 
EN61000-4-11 
Harmonic: EN61000-3-2 
Class 
 
IEEE 802.3at Interoperability 
UNH Interoperability report available on request 
 
FEATURE: 
Cisco Legacy detection 
No extern parts required for Legacy devices: 
VoIP Phones: 
7910,7912,7940,7960 
Access Points: 
350,1100,1200 
 
Over Voltage/Current, Short Circuit Protection
 
Outputs equipped with short circuit protection and 
overload protection as per 802.3at specifications 
The output can be shorted permanently without damage 
 
Over Temperature Protection 
Automatic Shutdown without damage 
 
Indicators 
Green LED: Power detected “CONNECT”  
Flashing GREEN: IEEE802.3af detected “CONNECT” 
at 15.4W 
Yellow LED: Fault detected 
 
USB Diagnostics Port and NIC Interface 
USB “B” port for diagnostics and manual port control 
Windows GUI 
NIC interface for remote management via secure IP 
access 
 
Input Connector 
AC Input IEC320 C14 
 
Warranty 
Limited Lifetime