With proper installation and maintenance, your new Gas Fireplace will provide years of trouble-free service. If you do experience a 
problem, refer to the troubleshooting guide below. This guide will assist a qualified service person in the diagnosis of problems and 
the corrective action to be taken.  Refer to page 24 for initial startup and GAS Line purge instructions.
SYMPTOM
CHECK
ACTION
No spark when system is turned to “ON” 
and reset cycle* has been completed.
Check for 120V between black “hot” line 
at  control  module  and  “white”  return  at 
module.
If 120V not present, check fuse or circuit 
breaker  or  repair  wiring  leading  to 
fireplace.
Spark for six (6) seconds at ignitor, but no 
ignition of burner. 
a. Check that gas is turned on and system 
purged.
Turn gas on and/or purge system.
b. Check that tips of ignitor are directly 
above ports on main burner. Spark is 
between  electrodes  and  not  from  one 
electrode to burner.
Position  electrodes  so  tips  are  directly 
above burner port ports and about ¼" to 
3
/
8
" above burner.
c. Check for 120V at each coil on the gas 
valve and listen for click, indicating gas 
valve is opening.
If  120V  present,  but  gas  valve  does  not 
click, replace gas valve.
Spark  for  six  (6)  seconds,  main  burner 
lights, but goes out when spark stops.
Check  for  clean  ground  path  between 
electrode  bracket  and  fireplace  chassis. 
Check  wiring  to  wiring  diagram  label. 
Check for broken electrode on high-tension 
lead attachment to module.
Clean, position according to wiring diagram, 
and repair defective electric connections. If 
all  electrical  connections  are  clean  and 
correct, replace module.
Main burner lights normally and then goes 
out.
a. Check ignitor to burner gap.
Igniter should be located 1/4" to 3/8" above 
burner area.
b. Check high-tension lead and connector 
for shorts. 
Replace spark electrode assembly.
c.  Refer  to  installation  instructions 
troubleshooting  guide  for  issues  such 
as venting.
Repair as required.
The conversion shall be carried out in accordance with the 
requirements of the provincial authorities having jurisdiction 
and in accordance with the requirements of the CSA B149.2 
installation code (Canada) and with the requirements of the 
National Fuel Gas Code Z223.1/NFPA 54 (United States).
WARNING:  This  conversion  kit  shall  be  installed  by  a 
qualified service agency in accordance with the manufacturer's 
instructions  and  all  applicable  codes  and  requirements 
of  the  authority  having  jurisdiction.  If  the  information  in 
this instruction is not followed exactly, a fire, explosion, or 
production of carbon monoxide may result causing property 
damage, personal injury, or loss of life. The qualified service 
agency is responsible for the proper installation of this kit. 
The installation is not proper and complete until the operation 
of  the  converted  appliance  is  checked  as  specified  in  the 
manufacturer's instructions supplied with the kit.
Installer notice: Using an ink pen, fill out the required information 
on the conversion label. Remove the backing from label and stick 
label  in  a  visible  position  on  bottom  of  fireplace  close  to  gas 
valve.
Installer  notice:  These  instructions  must  be  left  with  the 
appliance.
Instructions for converting your direct ignition fireplace from 
natural gas to propane/LP gas.
All direct ignition fireplaces are shipped from the factory equipped 
to operate on natural gas. To convert the direct ignition fireplace 
to operate on propane/LP gas, follow the instructions on Page  
26. Please see the appropriate parts list for your model for parts 
included with the direct ignition fireplace.
Check the items in the kit with the parts list. Notify the supplier of 
any items that are missing before installing the conversion kit.
DIRECT IGNITION TROUBLESHOOTING
DIRECT IGNITION PROPANE/LP GAS CONVERSION