Amtrol 600 LBC User Manual

Page of 4
EXPLOSION HAZARD. Failure to follow 
instructions in the accompanying product manual 
can cause rupture or explosion, possibly causing serious or fatal injury, 
leaking or flooding and/or property damage.
FAILURE TO PROPERLY SEAL VALVE CAP 
WILL RESULT IN LOSS OF PRECHARGE 
CAUSING PRODUCT TO FAIL.
Location of EXTROL
®
 Expansion Tanks
This Product, like most Products under pressure, 
may over time corrode, weaken and burst or 
explode, causing serious or fatal injury, leaking or flooding and/or 
property damage. To minimize risk, a licensed professional must install 
and periodically inspect and service the Product. A drip pan connected 
to an adequate drain must be installed if leaking or flooding could cause 
property damage. Do not locate in an area where leaking could cause 
property damage to the area adjacent to the appliance or to lower floors 
of the structure.
The AMTROL expansion tank may be placed in any convenient position 
within the mechanical room (or building).  If multiple tanks are installed, 
they should all be on the same level. 
Point of Connection 
Unlike a conventional tank, the EXTROL sealed air cushion does not 
require replenishment so DO NOT connect to an air separator or other 
air collection device. 
As with any expansion tank, it is recommended that the EXTROL be 
connected to the suction side of the pump. This will prevent the pump 
head from becoming subtractive which may result in entry of air and 
vapor formation at high points in the system. 
By connecting the EXTROL on the boiler return, displacement of coolest 
system water into tank is ensured reducing energy waste. 
Low pressure drop components such as air separators and boilers may 
be placed between point of connection and pump suction if desired. 
System design will dictate the feasibility of this.
Natural convection losses and the entry of air into tanks are eliminated by 
connection to the side or underside of main pipe. The piping should be pitched 
up and away from the EXTROL to eliminate any potential air traps.
Installation
THIS PRODUCT MUST BE INSTALLED BY A 
QUALIFIED PROFESSIONAL.
1.  Note location of system connection, air charge valve and drain 
connection on tank.
2.  Remove the plug or pipe cap from the system connection.
3.  Remove the 1 1/2” NPT plug covering the air charge valve.
4.  Before making any connection to the tank, check the tank and air 
charge (use an accurate pressure gauge). The air pressure must be 
equal to the minimum system pressure at the tank location.
IMPORTANT: If increasing pre-charge pressure above 
55 psig the following steps must be followed:
  a. Tank must be connected to the system with the isolation valve 
open.
  b. System must be pressurized to 13-14 psig, slightly above 
factory setting.
  c. Isolation valve needs to be shut.
  d. Pre-charge pressure of tank can now be increased to match 
system fill pressure.
  e. Open isolation valve and start up system.
 
Failure to follow these steps could result in damage to the 
bladder and void all warranties.
5. After making sure the air charge is correct, replace the valve cap and 
the 1 1/2” plug over the air valve.
6. The EXTROL may now be piped to the system (use the suggested 
EXTROL piping diagrams on the next page).
7. Using the table below, select appropriate pipe size. Connection to 
each EXTROL must have a lock shield gate valve and union to allow 
isolation and removal if required. Make up and fill valves, whether 
manual or automatic, should be tied into the connecting line. This will 
ensure that pump operation will not affect valve operation.
Operational Limits
Maximum Operating Pressure: As stamped on nameplate
Maximum Operating Temperature: 240 °F
Minimum Operating Temperature: 35°F (non-glycol application)
If unit is being installed in a glycol system where minimum temperatures 
fall below 35°F, contact the AMTROL technical service department at  
(401) 535-1216.
Operating Instructions
1. Check the expansion tank pre-charge before the system is filled with 
water. The charge is 12 psig unless noted otherwise on the tank label. 
Check to make sure this is the correct pre-charge pressure specified 
for the system.
2. If the tank pre-charge pressure needs to be changed on a dry system 
follow the following procedure:
  a. Check the expansion tank air pressures at the pre-charge 
connection with an accurate tire type pressure gauge. The 
pre-charge connection is the same kind of connection found on 
automobile tires.
  b.  If the pressure is low, charge the tank with nitrogen gas or with 
oil free compressed air. Check the pressure frequently during this 
process as you would when filling a tire with air.
DANGER: Excessive pressure can cause tank to 
explode. Exercise care when filling a tank with air so 
the pressure does not exceed that required or does 
not exceed the working pressure of the tank as stamped on the 
nameplate. Failure to follow these instructions will result in 
serious personal injury or death and property damage.
3. If, after the system has been filled with water and operating, it is found 
that the expansion tank pre-charge must be changed use the following 
procedure:
  a.  Turn off the heat source and allow the system water to cool to 
ambient temperature.
IMPORTANT: Expansion tank cannot be properly air 
charged other than at ambient temperature.
  b.  Close the lock-shield valve in the tank-to-system piping.
  c.  Open the drain valve to empty the water from the tank.
  d.  Check the tank air pressure at the pre-charge connection with an 
accurate tire type air gauge. 
  e.  Refer to 2b above.
  f.  Close the drain valve, open the lock-shield valve and turn on the 
heat source.
  g.  Relock the lock-shield valve.
PLEASE READ THE FOLLOWING INSTRUCTIONS CAREFULLY
IMPORTANT GENERAL SAFETY INFORMATION - 
ADDITIONAL SPECIFIC SAFETY ALERTS APPEAR IN THE FOLLOWING INSTRUCTIONS.
 
Firing Rate  
Length of Pipe Connecting
 
of Boiler 
Tank to System:
 
MBTU/H 
Below 11' 
11' – 30' 
31' – 100'
 2,000 
1
/
2
3
/
4
" 1"
 4,000 
3
/
4
"  1" 1
1
/
4
"
 8,000 
1" 
1
1
/
4
" 1
1
/
2
"
 12,000 
1
1
/
4
" 1 
1
/
2
" 2"
 16,000 
1
1
/
4
"  2" 2
1
/
2
"
 20,000 
1
1
/
2
"  2" 2
1
/
2
"
Warranty
LBC Series Models: One (1) Year Limited Warranty
Visit www.amtrol.com for complete warranty details.