IBM IBM UPS 10000XHV User Manual

Page of 29
15
 
N
OTE
:
 
S
ETTINGS ARE MADE THROUGH THE SUPPLIED 
P
OWER
C
HUTE 
B
USINESS 
E
DITION SOFTWARE
,
 
N
ETWORK 
M
ANAGEMENT 
C
ARD
,
 OR TERMINAL MODE
.
 
R
EFER TO THE SOFTWARE HELP GUIDES FOR DETAILS
. 
F
UNCTION
 
F
ACTORY
 
D
EFAULT
 
U
SER 
S
ELECTABLE 
C
HOICES
 
D
ESCRIPTION
 
Output Frequency 
Automatic 
(50 
±  3 Hz or 
60 
± 3 Hz) 
Automatic, 
50 
±  3 Hz, 
50 
±  0.1 Hz, 
60 
±  3 Hz, 
60 
±  0.1 Hz 
The user is able to set the allowable 
uninterruptible power supply output 
frequency. Whenever possible, the 
output frequency tracks the input fre-
quency. 
Number of Battery 
Packs 
Number of Con-
nected Battery Packs 
(four battery modules 
per pack) 
The user can define the number of con-
nected battery packs for proper runtime 
prediction. 
Emergency Power Off (EPO) Option 
The output power can be disabled in an emergency by closing a switch connected to the EPO. 
Note: Adhere to national and local electrical codes when wiring. 
The switch should be connected in a normally open switch contact. External voltage is not required; the switch is powered by a 
12 V internal power supply. A closed switch draws 2 mA of current. 
The EPO switch is internally powered by the uninterruptible power supply for use with non-powered switch circuit breakers. 
Note: The EPO circuit is considered a Class 2 circuit, (UL, CSA standards) and an SELV circuit (IEC standard). 
 
Both Class 2 and SELV circuits must be isolated from all primary circuitry. Do not connect any circuit to the EPO terminal 
block unless it can be confirmed that the circuit is Class 2 or SELV. 
If the circuit standard cannot be confirmed, use a contact closure switch.
 
Use one of the following cable types to connect the uninterruptible power supply to the EPO switch: 
• 
CL2: Class 2 cable for general use 
• 
CL2P: Plenum cable for use in ducts, plenums, and other spaces used for environmental air 
• 
CL2R: Riser cable for use in a vertical run in a floor-to-floor shaft 
• 
CLEX: Limited use cable for use in dwellings and for use in raceways 
• 
For installation in Canada: Use only CSA certified, type ELC (extra-low voltage control cable) 
• 
For installation in other countries: Use a standard low-voltage cable according to local regulations 
EPO 
Switch