Securing the Rack
The rack should be attached to the wiring closet floor with 3/8-inch (9.5 mm) lag screws or equivalent 
hardware. The floor under the rack should be level within 3/16-inch (5 mm). Use a floor-leveling 
cement compound if necessary or bolt the racks to the floor as shown in 
.
Figure 55: Properly Secured Rack
Brace open equipment racks if the channel thickness is less than 1/4 inch (6.4 mm).
Evaluating and Meeting Cable Requirements
This section addresses requirements for the cable you should use when installing your network 
equipment. It includes:
Cabling Standards
Extreme Networks recommends using the Building Industry Consulting Service International (BICSI) 
Registered Communications Distribution Designer (RCDD), which is globally recognized as a standard 
in site planning and cabling. For information, go to: