Extreme 3802 Installation Guide

Page of 394
 
Supplying Power to the Alpine 3802 DC Power Supply
Extreme Networks Consolidated "i" and "e" Series Hardware Installation Guide
167
Figure 92: Alpine 3804 DC power supply with cables 
5
Secure the cables using the lock washers and nuts.
6
Replace the plexiglas cover.
7
Turn on the DC supply at the wall breaker
8
Turn the on/off switch on the power supply to the on position.
Leave the ESD strap permanently connected to the chassis so that it is always available when you need 
to handle ESD-sensitive components.
Supplying Power to the Alpine 3802 DC Power Supply 
The Alpine 3802 switch supports two DC power supplies that come preinstalled from the factory. To 
power on the Alpine 3802 DC power supplies, complete the following tasks:
Select the cabling
Attach the cables and supply power 
For centralized DC power connections, install only in a restricted access area.
In the event of a power supply failure, contact Extreme Networks about servicing and replacing your 
power supply.
Selecting the Cabling
Use the following guidelines when selecting cabling for the DC power supplies:
Each DC power supply requires 6.5 A at -48 VDC nominal (or equivalent power between -40 and -70 
VDC).
For DC power and ground cables, use 14 AWG, high-strand-count copper wire cable.
Use power cables with the specifications outlined in Table 32. 
38_lugs4
45022
45022
SLIDE TO
REMOVE
ON
OFF
-48V
RTN
WHEN IN