Extreme Networks Consolidated "i" and "e" Series Hardware Installation Guide
Site Preparation
NOTE
Unshielded twisted pair (UTP) cable can build up ESD charges when being pulled into a new 
installation. Before installing category 5 UTP cables, discharge ESD from the cable by plugging it into a 
port on a switch or any network device that is not powered on.
Figure 11: Properly installed and bundled cable
Fiber Optic Cable
Fiber optic cable must be treated gently during installation. Every cable has a minimum bend radius, 
for example, and fibers will be damaged if the cables are bent too sharply. It is also important not to 
stretch the cable during installation. We recommend that the bend radius for fiber optic cable equals 
2-inch (5.08 cm) minimum for each 90 degree turn as shown in Figure 12.
SPG_008
Proper
bundling
of cables
Cable managers supporting
and directing cables
Adequate
slack, and
bend radius