Extreme 3802 Installation Guide

Page of 390
 
Meeting Power Requirements
Extreme Networks Consolidated "i" and "e" Series Hardware Installation Guide
51
DC Power Requirements
Table 9 lists DC power requirements for Extreme switches.
Table 8: AC power receptacle requirements
Switch Type
Country
Requirements
Alpine/Summit
North America
15 A service receptacle, NEMA 5-15 for 110/220 VAC power supplies.
Alpine/Summit
United Kingdom
10 A service receptacle, BS 1363 for 110/220 VAC power supplies.
Alpine/Summit
International
10 A service receptacle, CEE 7/7 for 110/220 VAC power supplies.
Alpine/Summit
Australia
10 A service receptacle, AS 3112 for 110/220 VAC power supplies.
Alpine/Summit
Japan
15 A service receptacle, JIS 8303 for 110/220 VAC power supplies.
BlackDiamond
North America
20 A service receptacle, NEMA L5-20 (locking) for BlackDiamond 110 
VAC power supplies.
BlackDiamond
North America
20 A service receptacle, NEMA L6-20 (locking) for BlackDiamond 220 
VAC power supplies.
BlackDiamond
International
16 A/20 A service receptacle, IEC 60309 for BlackDiamond 220 VAC 
power supplies.
BlackDiamond
North America
20 A service receptacle, NEMA 5-20 (non-locking) for BlackDiamond 110 
VAC power supplies.
BlackDiamond
North America
20 A service receptacle, NEMA 6-20 (non-locking) for BlackDiamond 220 
VAC power supplies.
BlackDiamond
International
16 A service receptacle, CEE 7/7 for BlackDiamond 220 VAC power 
supplies.
BlackDiamond
Australia
15 A service receptacle, 036 for BlackDiamond 220 VAC power supplies.
Table 9: DC power requirements
Switch Type
Country
Requirements
Alpine
International
Use 30 A at -40 V DC (or equivalent power between -40 and -70 V DC) for 
Alpine DC power supplies. 
For Alpine DC power and ground cables, use:
— 8 AWG, high strand-count copper wire cable (Alpine 3808)
— 10 AWG, high strand-count copper wire cable (Alpine 3804)
— 14 AWG, high strand-count copper wire cable (Alpine 3802)
BlackDiamond
International
Use 55 A service for BlackDiamond DC power supplies. 
For BlackDiamond DC power cables, use 4 AWG, high strand-count copper 
wire cable.
Summit48si
International
For the Summit48si DC power cable, use the three-wire harness that was 
shipped with the Summit48si switch and power supply.