3com 8807 Reference Guide

Page of 1099
894
C
HAPTER
 51: P
O
E PSU S
UPERVISION
 C
OMMANDS
poe-power 
output-thresh lower
Syntax
poe-power output-thresh lower string
View
System view
Parameter
string: Undervoltage alarm threshold. It ranges from 45.00 V to 47.00 V in the 
format of x.x.
Description
Use the poe-power output-thresh lower command to set the undervoltage 
alarm threshold of DC output (lower threshold):
For both 220 VAC and 110 VAC input, it is recommended to set the threshold to 
45.00 V.
Example
# Set the undervoltage alarm threshold of DC output to 45.00 V.
[SW8800] poe-power output-thresh upper 57.0
 
Set lower output-threshold power successfully! 
poe-power 
output-thresh upper
Syntax
poe-power output-thresh upper string
View
System view
Parameter
string: Overvoltage alarm threshold. It ranges from 55.00 V to 57.00 V in the 
format of X.X.
Description
Use the poe-power output-thresh upper command to set the overvoltage 
alarm threshold of DC output (upper threshold):
For both 220 VAC and 110 VAC input, it is recommended to set the threshold to 
57.00 V.
Example
# Set the overvoltage alarm threshold of DC output to 57.00V.
[SW8800] poe-power output upper 57.00
 
Set upper output-threshold power successfully!