Use a rack that supports approximately 600 lb 
(272 kg).
Use a rack that has adequate electrical 
grounding, for instance, with a distribution rack 
grounding kit.
Verify that the floor under the rack is level 
within 
3
/
16
 inch (5 millimeters). Use a 
floor-leveling cement compound if necessary or 
bolt the racks to the floor. 
Attach the rack to the wiring closet floor with 
3
/
8
 inch (9.5 millimeters) lag screws or equivalent 
hardware. 
Brace open distribution racks if the channel 
thickness is less than 
1
/
4
 inch (6.4 millimeters).