3com S7906E Quick Setup Guide

Page of 155
 
3-4 
If there is a grounding strip in the Ethernet switch installation environment, attach one end of the 
yellow-green protection grounding cable to the grounding screw of the grounding strip and fasten 
the captive nuts. The grounding cable of a switch shall be connected to the project ground of the 
equipment room. 
Figure 3-3 Connect the protection grounding cable to the grounding strip 
Power input
Ethernet 
Switch
Grounding strip
Protection  grounding cable
Grounding screw
Ethernet 
Switch
Ethernet 
Switch
 
 
If there is no grounding strip but earth nearby and the grounding body is allowed to be buried, you 
can simply hammer an angle iron or steel pipe no shorter than 0.5m into the earth. In this case, the 
yellow-green protection grounding cable should be welded with the angle iron (steel pipe) and the 
joint should be processed against eroding. 
Figure 3-4 Connect the protection grounding cable to the grounding body nearby 
Power input
Ethernet Switch
Grounding screw
Angle steel
Ground
Protection  grounding cable
 
 
If there is no grounding strip and no grounding body can be buried, the AC-powered Ethernet 
switch can be grounded through the PE wire of the AC power supply. In this case, make sure that 
the PE wire of the AC power supply has been well grounded at the power distribution room or AC 
power supply transformer side.