Eaton TPC2365/MTD User Manual

Page of 5
© 2008 Eaton Corporation. All Rights Reserved. All specifications are subject to change without notice.
www.pulizzi.com • pulizzisales@eaton.com • 800-870-2248 • Fax: 605-334-4999 
2
RACK MOUNTED
19” x 1U (1.72”) x 7”
Approximate shipping weight: 9 lbs.
TPC2365-2980 and TPC2365-3732 
are 9.5” deep
EMI/RFI FILTER
Differential Mode - Line to Line
Common Mode - Line to Ground
SPIKE/SURGE SUPPRESSION
Line to Line
IEC 60320 C20 Power Inlet
Power inlet is on the rear panel  
Rated by UL/CSA at 125VAC/20A or    
250VAC/16A Rated by TUV at  
 
250VAC/16A
IEC 60320 OUTLETS (12)
Three sections of (4) switched outlets on 
the rear panel.  Each group of four  
 
outlets are:
– Rated by UL/CSA up to 250VAC/15A
– Rated by VDE at 250VAC/10A
REMOTE SELECTION SWITCH
Local: Power “on or off” to the switched   
outlets
Off: When breaker is “on” but this switch 
is in the “off” mode, you will not have    
power to the outlets
Remote: Power “on or off” to the  
 
switched outlets via a remote device
Latching remote on “LT” models only,    
the selection switch is wired for  
 
Remote/Off/Remote - There is no local   
control
REMOTE INTERFACE
Remote on/off and EPO control - EPO    
overrides remote and local control
Sequence Power Up additional 
equipment down line (standard on all units
Latching remote “LT” models only -  
 
normally closed EPO, momentary start
MULTIPLE TIME DELAY (MTD™) (Optional)
Activated “Locally” or “Remotely”,  
 
Section 1 powers up, followed 
4-seconds later by Section 2 which is    
followed 4-seconds later Section 3
then 4-seconds later the sequenced  
 
remote activates the next system in line
INDICATOR LIGHTS (5)
Power to Section 1, 2 and 3
115 VAC or 230VAC input selected
OVERLOAD CIRCUIT PROTECTION
Electromagnetic breaker provides manual 
on/off switching and trips in an overload 
condition
AUTO-VOLTAGE SELECTION
The AVS
TM
 system automatically senses 
the input voltage and adjusts the internal 
components to use that voltage for the output
SPECIFICATIONS
TPC2365
TPC2365/MTD
TPC2365-LT
TPC2365/LT
TPC2365-2980
TPC2365-3732
Approvals
cTUVus, CE
cTUVus, CE
cTUVus, CE
cTUVus, CE
NA
NA
Voltage Input/Output, 
(50/60Hz)
110-125V
200-240V
110-125V
200-240V
110-125V
200-240V
110-125V
200-240V
110-125V
200-240V
200-240V
Current Input
20A
20A
20A
20A
30A
30A
Current Output 
16A
16A
16A
16A
24A
24A
Full Load VA
1920VA / 3840VA
1920VA / 3840VA
1920VA / 3840VA
1920VA / 3840VA
2880VA / 5760VA
5760VA
Circuit Breaker
2 Pole 20A
2 Pole 20A
2 Pole 20A
2 Pole 20A
(3) 2 Pole 10A
(3) 2 Pole 10 A
Multiple Time Delay
NO
YES
NO
YES
YES
YES
EMI/RFI Filter
YES (20A)
YES (20A)
YES (20A)
YES (20A)
YES (30A)
YES (30A)
Surge Suppression
320V
320V
320V
320V
320V
320V
Outlets
IEC 60320
Type C13
IEC 60320
Type C13
IEC 60320
Type C13
IEC 60320
Type C13
IEC 60320
Type C13
IEC 60320
Type C13
Remote Control
Standard
Standard
Latching
Latching
Latching
Latching
Power Cable
Not Included
Not Included
Not Included
Not Included
10/3, 15’
10/3, 15’
Power Input
C20 Inlet
C20 Inlet
C20 Inlet
C20 Inlet
Bare Wire
L6-30P
TPC2365-LT Front
TPC2365-LT Front