CABLE ASSEMBLY OPTIONS:
CBL113: 10/5 cable 9’ long terminated with a NEMA L21-30P at
one end and a mating IEC 60309 connector at the other end.
For use in North America at 120/208V~
one end and a mating IEC 60309 connector at the other end.
For use in North America at 120/208V~
CBL114: 5x4.0mm Harmonized cable 9’ long with an
IEC 60309 connector at both ends.
For use in Europe at 230/400V~
IEC 60309 connector at both ends.
For use in Europe at 230/400V~
RACK MOUNTED
•
19” x 5.25” (3U) x 16.5” with recess
mounting
mounting
•
Approximate shipping weight: 41 lbs.
POWER INPUT
•
5’ Power cable with IEC 309 plug is
attached to unit through the front panel
cable grip
attached to unit through the front panel
cable grip
•
Unit ships with mating connector to
IEC 60309 outlets on front panel
IEC 60309 outlets on front panel
EMI/RFI FILTERING
•
Common Mode - Line to Ground
•
Differential Mode - Line to Line
(17) IEC OUTLETS
(12) C13 Type:
(12) C13 Type:
•
120/208V Input, the output is 120V
•
230/400V input, the output is 230V
(4) C19 Type:
•
120/208V input, the output is 208V
•
230/400V input, the output is 230V
(1) IEC 309 3-Phase/30A:
•
120/208V input, the output is 120/208V
•
230/400V input, the output is 230/400V
(3) INDICATOR LIGHTS
•
Power “on” to PH-X, -Y, -Z
BRANCH CIRCUIT PROTECTION
•
UL489 Listed Main Disconnect breakers,
with a long time delay curve, provide
manual on/off switching and automatically
trip with an overload condition
with a long time delay curve, provide
manual on/off switching and automatically
trip with an overload condition
(4) REMOTE I/O PORTS
•
2 Front / 2 Rear: one on each side is
sequence and the other is for remote
on/off and EPO control. The PC2672 is
controlled remotely only
sequence and the other is for remote
on/off and EPO control. The PC2672 is
controlled remotely only
•
Latching remote - (N/C) EPO between
pins 2 & 3, momentary start between
pins 1 & 3
pins 2 & 3, momentary start between
pins 1 & 3
SPECIFICATIONS
PC2672
Voltage Selectable Input Three Phase (50/60Hz)
120/208V~ or 230/400V~
Voltage Output Single Phase on C13s (50/60Hz)
120V~ or 230V~
Voltage Output Single Phase on C19s (50/60Hz)
208V~ or 230V~
Voltage Output Three Phase on IEC 309 (50/60Hz)
120/208V~ or 230/400V~
Current Input Per Phase
30A Per Phase
Current Output Per Phase
24A Per Phase
Full Load VA Per Phase
2880VA at 120/208V or 5520VA at 230/400V Per Phase
Main Listed Breaker
30/30/30A
Secondary Listed Breakers, (1) Each For The C19 Outlets
(4) 16/16A
Secondary Listed Breakers, (1) Each For A Pair of C13 Outlets
(6) 10A
IEC 60320 Type C13 Outlets
(12) 15A/125V or 10A/250V
IEC 60320 Type C19 Outlets
(4) 20A/125V or 16A/250V
IEC 309 Outlet
(1) 3 phase/30A
EMI/RFI Filter
30A
Power Cord/Length/Plug
10/5, 5’, IEC 60309 3P+N+PE, 30A