Eaton TPC4100-C User Manual

Page of 4
© 2008 Eaton Corporation. All Rights Reserved. All specifications are subject to change without notice.
www.pulizzi.com • pulizzisales@eaton.com • 800-870-2248 • Fax: 605-334-4999 
2
CHASSIS
19” x 1.72” (1U) x 9.5”
Approximate shipping weight: 19 lbs.
Detachable mounting brackets allow for 
several mounting options
EMI/RFI FILTERING
Common Mode - Line to Ground
Differential Mode - Line to Line
SPIKE/SURGE SUPPRESSION
Line to Line
BRANCH CIRCUIT PROTECTION
UL489 Listed electromagnetic breakers, 
with a long time delay curve, provide    
both manual on/off switching and open   
(trip) automatically with an overload  
 
condition
(3) INDICATOR LIGHTS
Provided for each phase power “ON” via 
breaker
(12) NEMA OUTLETS
(4) Per phase PH-Y and PH-Z on the rear 
panel and PH-X has two on the rear and 
2 on the front panels
POWER INPUT
Power cable with locking plug is  
 
attached to the unit through the rear  
 
panel cable grip
SPECIFICATIONS
TPC4100-A2
TPC4100-B
TPC4100-AB
TPC4100-C
TPC4100-D
Approvals
UL/cUL Listed
UL/cUL Listed
UL/cUL Listed
UL/cUL Listed
UL/cUL Listed
AC Voltage Input 
(50/60Hz)
120/208V WYE
120/208V WYE
120/208V WYE
120/208V WYE
120/208V WYE
AC Voltage Output
120V~
208V~
120V~ and 208V~
120V~
120V~
Current Input
20A
Per Phase
30A
Per Phase
30A
Per Phase
30A
Per Phase
30A
Per Phase
Current Output
16A
Per Phase
24A
Per Phase
24A
Per Phase
24A
Per Phase
24A
Per Phase
Full Load VA 
Per Phase
1920VA
Per Phase
2880VA
Per Phase
2880VA
Per Phase
2880VA
Per Phase
2880VA
Per Phase
NEMA Outlets
(12) 5-20R
(12) 6-15R
(6) 5-15R, (6) 6-15R (12) 5-15R
(12) 5-20R
Listed Circuit Breaker
(3) 1 pole/20A
(3) 2 pole/15A
(3) 2 pole/15A
(3) 2 pole/15A
(3) 2 pole/20A
Remote
NO
NO
NO
NO
NO
EMI/RFI Filter
30A
30A
30A
30A
30A
Surge Suppression
150V
270V
150V
150V
150V
Cable
12AWG/5wire, 9’
10AWG/5wire, 9’
10AWG/5wire, 9’
10AWG/5wire, 9’ 10AWG/5wire, 9’
NEMA Power Input
L21-20P
L21-30P
L21-30P
L21-30P
L21-30P
TPC4100-AB Rear