Option 2: Circuit Breaker
This unit is available with or without a circuit breaker. The circuit breaker provides supplementary overload protection to the devices connected to the 
T2235. For mission critical applications, the T2235 can be ordered without a circuit breaker, preventing a single point of failure. Select “C” in this option to 
include the circuit breaker or “N” to not include it. (Circuit breakers are mandatory in C1, C2, F3, F4 versions.)
Option 4: Color and Mounting
Powder Coat Black finish with adjustable mounting options.
Option 3: EMI/RFI Filtering
Select “F” for filtering and “N” for no filtering.
T2235 Series
Version
Voltage/Current
Input/Output Rating
Input Connectors
  Straight Blade            Twist Lock
Output Connectors
  Straight Blade
A1
120V, 12A
A2
120V, 16A
AB
100-240V, 16A
C1
120V, 24A
(1) 2 Pole 15A UL listed CB
is required for branch protection
C2
120V, 24A 
(1) 2 Pole 20A UL listed CB
is required for branch protection
F3
200-240V, 24A
(2) 2 Pole 15A UL Listed CB
is required for branch protection
F4
200-240V, 24A
(2) 2 Pole 15A UL Listed CB
is required for branch protection
NA
NA
NA
NA
NA
Option 1: Voltage and Current Configuration
The following chart shows the available input/output voltage and current configurations. Most options have a choice of 
straight blade or twist lock connectors. This selection is made in options 3 and 4.
Option 5: Power Cable and Plug Type
Choose either straight blade or twist lock style plug. See the table in Option 1 for a view of the available plug styles. Verify you have the correct type of 
mating receptacle available at your facility. Plug types sometimes limit the available voltage and current options. The AB version is available only with 
the C20 power inlet. The power cables for this version must be ordered separately.